Troubleshooting

9. Troubleshooting
MALFUNCTION
The app does not find the room
thermostat during teach-in.
The display shows the message "F"
pulsating every 10 seconds for 1
second.
The message "F1" appears in the
display.
The message "F3" appears in the
display.

10. Maintenance

WARNING
Danger to life due to electric current !
Penetrating liquids can cause electric shocks and
fires.
!
If necessary, clean the surfaces with a soft cloth.

11. Disposal

Directive 2012/19/UE WEEE:
The "crossed-out wheeled bin" symbolises that your are legally obliged to dispose of old appliances separately
from unsorted municipal waste. Incorrect disposal can lead to environmental damage.
Remove used batteries and accumulators not enclosed in the old appliance as well as lamps from the old appli-
ance without destroying them and dispose of them separately.
You can hand in your old appliance free of charge within the framework of the possibilities provided by the pub-
lic waste disposal authorities.
Distributors with a sales area for electrical and electronic equipment of at least 400 square meters are obliged
to take back your old appliance free of charge when you buy a similar new appliance (1:1 take-back). You can
also return all old appliances to distributors free of charge if the external dimensions do not exceed 25 centime-
tres and the return is limited to three old appliances per type of appliance.
Delete your personal data stored on the old device to be disposed of, if any, on your own responsibility.
22
CAUSE
Other devices equipped with Blue-
tooth interfere with the connection
between the room thermostat and
smartphone.
The temperature measured at the in-
ternal temperature sensor has
dropped below 6 °C (43 °F).
The frost protection function is acti-
vated (two point / PWM) is switched
on).
The device has measured implausible
temperature values or the tempera-
ture measurement has failed.
Auto mode cannot be activated be-
cause no correct time and date infor-
mation is stored in the ClimaCon.
REMEDY
During the teach-in process, temporarily
switch off all Bluetooth-equipped devices
that are not needed.
If the temperature measured at the internal
temperature sensor rises above 6 °C (43 °F),
the frost protection function is automatical-
ly deactivated.
Contact the technical service.
Connect your ClimaCon to your smart-
phone via Bluetooth. Valid time and date in-
formation is transferred from the
smartphone to the ClimaCon.