oventrop ClimaCon F Operating Instructions Manual page 14

Table of Contents

Advertisement

ClimaCon F
Mounting
6.4.1.2 ClimaCon F 100 (230 V) (item no. 1155010)
Terminal
Assignment
1
IN (L 230 V) operating voltage
2
IN (N 230 V) operating voltage
3
OUT (L 230 V) on/off / PWM
IN (L 230 V) setback input,
4
not potential-free
IN (L 230 V) change-over, not poten-
5
tial-free
1
2
L
N
L
N
6.4.1.3 ClimaCon F 100 (24 V) (item no. 1155510)
Terminal
Assignment
1
IN (L1 24 V AC) operating voltage
2
IN (L2 24 V AC) operating voltage
3
OUT (L1 24 V AC) on/off / PWM
IN (L1 24 V AC) setback input,
4
not potential-free
IN (L1 24 V AC) change-over,
5
not potential-free
1
2
L1
L2
L1
SELV
L2
14
3
4
5
CO
L
L
3
4
5
CO
L1
L1
6.4.1.4 ClimaCon F 210 (230 V) (item no. 1155021)
Terminal
Assignment
1
IN (L 230 V) operating voltage
2
IN (N 230 V) operating voltage
3
OUT (L 230 V) on/off / PWM
4
OUT (L 230 V) setback output
1
2
3
L
N
L
N
6.4.1.5 ClimaCon F 310 (230 V) (item no. 1155031)
Terminal
Assignment
1
IN (L 230 V) operating voltage
2
IN (N 230 V) operating voltage
3
OUT (L 230 V) on/off / PWM
4
OUT (L 230 V) setback output
5
IN (L 230 V) change-over, not potential-free
OUT (NO) potential-free contact
9
(max 230 V, 90 mA DC/AC)
OUT (COM) potential-free contact
10
(max 230 V, 90 mA DC/AC)
1
2
3
4
L
N
L
N
4
L
5
9
10
CO
NO
COM
DI
(ON/
OFF)
L
L
115500984-V07.11.2022

Advertisement

Table of Contents
loading

Table of Contents