<1>. Verify the type of refrigerant used by the unit to be serviced.
Refrigerant Type: R410A
<2>. Check the symptom exhibited by the unit to be serviced.
Look in this sercice handbook for sympeoms relating to the refrigerant cycle.
<3>. Be sure to carefully read the Safety cautions at the beginning of this document.
<4>. If there is a gas leak or if the remaining refrigerant is exposed to an open flame, a
noxious gas hydrofluoric acid may form. Keep workplace well ventilated.
Install new pipes immediately after removing old ones to keep moisture out of the
refrigerant circuit.
Chloride in some types of refrigerants such as R22 will cause the refrigerating
machine oil to deteriorate.
Necessary Tools and Materials
Prepare the following tools and materials necessary for installing and servicing the unit.
[Necessary tools for use with R410A(Adaptability of tools that are for use with R22 and
R407C)]
1. To be used exclusively with R410A ( Not to be used if used with R22 or R407C )
Tools/Materials
Gauge Manifold
Charging Hose
Refrigerant Recovery
Equipment
Refrigerant Cylinder
Refrigerant Cylinder
Charging Port
Flare Nut
CAUTION!
Use
Evacuating,refrigerant charging 5.09MPa on the High-pressure side.
Evacuating, refrigerant charging Hose diameter larger than the
Refrigerant recovery
Refrigerant charging
Refrigerant charging
Connecting the unit to piping
8
Notes
concentional ones.
Write down the refrigerant type.
Pink in color at the top of the cylinder.
Hose diameter larger than the
conventional ones.
Use Type-2 Flare nuts.