R-410A
DPX024-048
DPY060
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Rigging And Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Roof Curb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Service Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Power And Control Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . 8
1 Unit Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 Unit Accessory Weights . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3 Unit Dimensions Front . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
6 Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
7 Side Duct Application . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
8 Bottom Duct Application . . . . . . . . . . . . . . . . . . . . . . . . . 13
9 Additional Static Resistance . . . . . . . . . . . . . . . . . . . . . . 14
10 Electric Heat Minimum Supply Air . . . . . . . . . . . . . . . . . . 15
11 Indoor Blower Specifications . . . . . . . . . . . . . . . . . . . . . . 15
1 Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 Unit 4 Point Load Weight . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 Dimensions Front and Bottom . . . . . . . . . . . . . . . . . . . . . 6
5 Dimensions Back and Bottom . . . . . . . . . . . . . . . . . . . . . 6
6 Roof Curb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Stage Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

General

Models DPX and DPY units are factory assembled cooling units
designed for outdoor installation on a roof top or a slab. Field-
installed electric heater accessories are available to provide
supplemental electric heat combined with electric cooling.
The units are completely assembled on rigid, removable base
rails. All piping, refrigerant charge, and electrical wiring is
factory installed and tested. The units require only electric
power and duct connections at the point of installation.
The electric heaters have nickel-chrome resistance wire
elements and utilize single point power connection.
Safety Considerations
This is a safety alert symbol
labels or in manuals, be alert to the potential for personal injury.
Understand and pay particular attention the signal words
DANGER, WARNING or CAUTION.

TABLE OF CONTENTS

LIST OF TABLES
LIST OF FIGURES
. When you see this symbol on
Compressors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Phasing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Blower Speed Selection . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Cooling Sequence Of Operations . . . . . . . . . . . . . . . . . . . 18
Heating Sequence Of Operations . . . . . . . . . . . . . . . . . . . 18
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Normal Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
12 Electric Heat Multipliers . . . . . . . . . . . . . . . . . . . . . . . . . 15
13 DPX024 Superheat Charging . . . . . . . . . . . . . . . . . . . . . 16
14 DPX030 Superheat Charging . . . . . . . . . . . . . . . . . . . . . 16
15 DPX036 Superheat Charging . . . . . . . . . . . . . . . . . . . . . 16
16 DPX042 Superheat Charging . . . . . . . . . . . . . . . . . . . . . 16
17 DPX048 Superheat Charging . . . . . . . . . . . . . . . . . . . . . 17
18 DPY060 Superheat Charging . . . . . . . . . . . . . . . . . . . . . 17
19 Delay Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
9 Typical Field Power Wiring Diagram . . . . . . . . . . . . . . . . 9
10 Control Board Speed Tap Location . . . . . . . . . . . . . . . . 18
11 R-410A Quick Reference Guide . . . . . . . . . . . . . . . . . . 24
DANGER indicates an imminently hazardous situation, which,
if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which,
if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if
not avoided may result in minor or moderate injury. It is also
used to alert against unsafe practices and hazards involving
only property damage.
Improper installation may create a condition where the
operation of the product could cause personal injury or
property damage. Improper installation, adjustment,
alteration, service or maintenance can cause injury or
property damage. Refer to this manual for assistance or
for additional information, consult a qualified contractor,
installer or service agency.
SO 9001
Certified Quality
Management System
288591-BIM-C-0408

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DPX024-048 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Johnson Controls DPX024-048

  • Page 1: Table Of Contents

    R-410A DPX024-048 DPY060 SO 9001 Certified Quality Management System 2-5 Ton TABLE OF CONTENTS General ......... . 1 Compressors.
  • Page 2 Reference Additional information is available in the following reference forms: • Technical Guide - DPX024-048, DPY060, 294605 Before performing service or maintenance operations on • General Installation - DPX024-048, DPY060, 288591 unit, turn off main power switch to unit. Electrical shock •...
  • Page 3: Installation

    Table 1: Unit Limitations Unit Limitations Size Model Unit Voltage Applied Voltage Outdoor DB Temp (Tons) Max (°F) 208/230-1-60 (2.0) 208/230-1-60 (2.5) 208/230-1-60 208/230-3-60 (3.0) 460-3-60 208/230-1-60 208/230-3-60 (3.5) 460-3-60 208/230-1-60 208/230-3-60 (4.0) 460-3-60 208/230-1-60 208/230-3-60 (5.0) 460-3-60 Johnson Controls Unitary Products...
  • Page 4: Location

    49-1/8 47-1/4 Figure 2: Unit 4 Point Load Weight Weight (lbs.) Center of Gravity 4 Point Load Location (lbs.) Size Model (Tons) Shipping Operating 22.25 (2.0) 22.25 (2.5) 22.25 (3.0) 22.25 (3.5) 22.25 (4.0) 22.25 (5.0) Johnson Controls Unitary Products...
  • Page 5: Unit Accessory Weights

    For all other heaters, zero inch clearance all sides for entire length of duct. Note: For units applied with a roof curb, the minimum clearance may be reduced from 1 inch to 1/2 inch between combustible roof curb material and this supply air duct. Johnson Controls Unitary Products...
  • Page 6: Dimensions Front And Bottom

    SIDE SUPPLY 14-1/2 AIR OPENING 28-3/8 CONDENSER COIL 14-1/2 BACK BOTTOM SUPPLY AIR OPENING 3-3/8 SIDE RETURN AIR OPENING 14-1/2 3-1/2 1-3/4 1-3/4 BOTTOM RETURN 28-9/16 3-1/2 AIR OPENING 1-3/4 Figure 5: Dimensions Back and Bottom Johnson Controls Unitary Products...
  • Page 7: Ductwork

    Use a sealing compound on male pipe threads. Install the DO NOT insert the screws through the casing. Outdoor condensate drain line (3/4” NPTF) to spill into an open drain. duct work must be insulated and waterproofed. 1. 8” Roof Curb also available. Johnson Controls Unitary Products...
  • Page 8: Service Access

    ** = Minimum wire size of 18 AWG wire should be used for all field JUMPER NEEDED FOR FULL SPEED installed 24 volt wire. COMPRESSOR OPERATION 24 VOLT TRANSFORMER PROGRAMMABLE THERMOSTAT ONLY Figure 7: Typical Field Control Wiring Diagram Single Stage Thermostat Johnson Controls Unitary Products...
  • Page 9: Electrical Data

    73.1 / 83.5 80 / 90 None 19.4 (3.0) 208/230-3-60 11.1 2NH04501025 7.5/10 20.8/24.1 31.4 / 35.4 35 / 40 2NH04501525 11.3/15 31.3/36.1 44.5 / 50.5 45 / 60 None 10.7 460-3-60 2NH04501046 20.4 2NH04501546 27.9 Johnson Controls Unitary Products...
  • Page 10: Physical Data

    28.6 36.0 43.5 49.0 58.5 12.3 12.3 12.3 12.3 12.3 11.6 SEER 14.5 Nominal CFM 1000 1150 1400 1600 1750 System power (KW) Refrigerant type R-410a R-410a R-410a R-410a R-410a R-410a Refrigerant charge (lb-oz) 10-0 10-8 Johnson Controls Unitary Products...
  • Page 11: Compressors

    (leading to cracking) to occur in one year precautions to avoid exposure of the oil to the atmosphere. or more. When performing any service that may risk exposure of compressor oil to the roof, take precautions to protect roofing. Johnson Controls Unitary Products...
  • Page 12: Side Duct Application

    1200 HEAT-B 1080 Heat HEAT-C 1275 HEAT-D 1200 COOL-A COOL-B COOL-C COOL-D Cool Y1+Y2 COOL-A 1400 Y1+Y2 COOL-B 1200 High (3.5) Y1+Y2 COOL-C 1300 Y1+Y2 COOL-D 1500 HEAT-A 1225 HEAT-B 1100 Heat HEAT-C 1350 HEAT-D 1225 Johnson Controls Unitary Products...
  • Page 13: Bottom Duct Application

    HEAT-A 1000 HEAT-B Heat HEAT-C 1100 HEAT-D 1000 COOL-A COOL-B COOL-C COOL-D Cool Y1+Y2 COOL-A 1200 Y1+Y2 COOL-B 1000 High (3.0) Y1+Y2 COOL-C 1100 Y1+Y2 COOL-D 1300 HEAT-A 1200 HEAT-B 1080 Heat HEAT-C 1275 HEAT-D 1200 Johnson Controls Unitary Products...
  • Page 14: Additional Static Resistance

    0.02 0.03 0.01 0.01 0.02 0.03 0.01 0.01 0.02 0.04 1000 0.02 0.01 0.02 0.04 1100 0.03 0.01 0.03 0.05 (3.0) 1200 0.04 0.02 0.03 0.06 1300 0.04 0.03 0.03 0.07 1400 0.04 0.04 0.03 0.08 Johnson Controls Unitary Products...
  • Page 15: Ton

    (2.0) 0.92 0.92 Variable (2.5) 1. Electric heaters are rated at nominal voltage. Use this table to Variable (3.0) determine the electric heat capacity for heaters applied at lower voltages. Variable (3.5) Variable (4.0) Variable (5.0) Johnson Controls Unitary Products...
  • Page 16: Dpx024 Superheat Charging

    11.4 12.4 12.9 13.4 10.1 10.3 10.4 10.6 10.7 10.9 12.0 13.1 13.6 14.1 10.5 10.7 10.8 10.9 11.1 11.2 11.4 12.5 13.7 14.3 14.9 11.1 11.2 11.3 11.4 11.6 11.7 11.8 13.1 14.4 15.0 15.6 Johnson Controls Unitary Products...
  • Page 17: Blower Speed Selection

    Find the recommended system airflow for the unit model. Set desired cooling airflow by moving the jumper on the “Cool” tap located on the CFM selection board as indicated in Tables 7, 8 and Figure 10. Johnson Controls Unitary Products...
  • Page 18: Operation

    Only a power cycle will clear this state. If the 2-stage thermostat calls for the second stage of cooling, the 24 volts at "Y2" signals the ECM controller to Johnson Controls Unitary Products...
  • Page 19: Thermostat Signals (Single Phase Units)

    HEATER BANK 4, 5 & 6 ELEC. HEAT 10 SEC. DELAY ON HEATER BANK 4, 5 & 6 ELEC. HEAT INSTANT OFF HEATER BANK 1, 2 & 3 ELEC. HEAT 1/2 SEC. DELAY OFF BLOWER 60 SEC. DELAY OFF Johnson Controls Unitary Products...
  • Page 20: Maintenance

    The wire number or color and terminal designations referred to may vary. Check the wiring label inside the control box access panel for the correct wiring. Johnson Controls Unitary Products...
  • Page 21: Typical Wiring Diagrams

    288591-BIM-C-0408 Typical Wiring Diagrams Typical DPX024-048, DPY060 Cooling Only 208/230-1-60 volt Wiring Diagram Johnson Controls Unitary Products...
  • Page 22 288591-BIM-C-0408 Typical DPX036-048, DPY060 Cooling Only 208/230-3-60 volt Wiring Diagram Johnson Controls Unitary Products...
  • Page 23 288591-BIM-C-0408 Typical DPX036-048, DPY060 Cooling Only 460-3-60 volt Wiring Diagram Johnson Controls Unitary Products...
  • Page 24: 410A Quick Reference Guide

    Figure 11: R-410A Quick Reference Guide Subject to change without notice. Printed in U.S.A. 288591-BIM-C-0408 Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: 288591-BIM-B-0807 Johnson Controls Unitary Products 5005 York Drive Norman, OK 73069...