1. Fit solar connection kit EKSOLHWAV1 to hot water storage tank. See installation instructions for solar connection kit.
2. Install the solar module EKRP1HBAA in the internal unit of the air-water heat pump EKHBH*/ EKHBX*. See installation
instructions for solar module.
3. Fit solar panel temperature sensor. See installation instructions for solar panels EKSV26P/ EKSH26P.
3.3

Pump unit EKSRDS1A

Fig. 3-4
EKSR3PA + EKSRDS1A
Control and pump unit for solar systems
4PW56033-1
DANGER!
Leaking gas in the immediate proximity of electrical components can cause an explosion.
The Control and pump unit for solar systems EKSR3PA + EKSRDS1A and electrical components should
not be installed in locations where there is a danger of flammable gas escaping.
Pay attention to minimum distances from walls and in shafts.
CAUTION!
If the circulation in the solar panels comes to a standstill, steam may be formed and may damage the
diaphragm expansion vessel (MAG).
• Always install the EKSRDS1A pump unit and the diaphragm expansion vessel (MAG) lower than the solar
panels.
EKHB*
CAUTION!
Danger of scalding if incorrect connection pipes are used.
• The connection pipe between the solar panel array and the hot water storage tank must be made of
pressure-resistant metal piping (recommended Cu Ø 22 mm). Using plastic piping is not allowed.
14
Connections and dimensions pump unit EKSRDS1A
EKSRDS1A
1
Outside cover
2
Temperature gauge on solar return line
3
Temperature gauge on solar feed line
4
Connection of solar return line (Ø 22 mm)
5
Connection of solar feed line (Ø 22 mm)
6
Safety valve with pressure gauge (solar panel circuit)
7
Connection of diaphragm expansion vessel (MAG) (Ø 22 mm)
8
Circulation pump (solar panel circuit)
9
Filling and drainage cock (solar panel circuit)
10
Flowmeter (solar panel circuit)
11
Connection of pump unit feed pipe to solar connection kit
EKSOLHWAV1 (Ø 22 mm)
12
Connection of pump return line to solar connection kit
EKSOLHWAV1 (Ø 25 mm)
13
Drilled holes for mounting the pump unit on the wall
14
Venting pot
3
x
Installation
EKHB*
EKSRDS1A
Operating and installation instructions