Download Print this page
LEGRAND bticino FL4653 Manual

LEGRAND bticino FL4653 Manual

Bedside panel bus-scs

Advertisement

Quick Links

Bedside panel
BUS-SCS
1. DESCRIPTION
The bedside panel is dedicated to hotels. It has a thermostat function
which can be used on heating and/or air conditioning installations, 5
scenario control units and a "Do not disturb" housekeeping function. It
is possible to display and set the reference temperature, fan speed, and
switch ON with thermal overload protection.
The screen displays the measured ambient temperature or the reference
temperature.
It indicates and can be used to activate the housekeeping information:
- Do Not Disturb
- Make up room: only available on configured version.
It has a proximity sensor which can be disabled by configuration: when
the device detects an approach, it switches from standby state to active
state. The LED brightness level (on standby or active) and the time delay
before returning to standby state can also be set by configuration.
The control & management software is used to view and control the
thermostat. Configuration is possible with the MyHotel_Suite software
on SCS installations which include the MH201 device, or with the Hotel
Room Controller Software on IP installations which include the 0 484 08
or 0 484 12 device.
Front view
2
3
1
9
8
Key
1. Scenario buttons
2. Heating enabled indicator
(red) Air conditioning enabled
indicator (blue)
3. MODE button: pressing briefly
changes from normal mode (ON)
to protection mode (frost guard
or thermal overload).
A longer press changes
the function (heating/air
conditioning/automatic)
according to the configuration.
4. Measured temperature (SET off )
or reference temperature (SET on)
indicator
Technical data sheet: S000102895EN-1
128, av. du Maréchal-de-Lattre-de-Tassigny - 87045 LIMOGES Cedex
Tel: +33(0)5 55 06 87 87 Fax: +33(0)5 55 06 88 88
www.legrand.com
Rear view
4
5
6
7
10 11
5. + button: increases the reference
value
6. – button: decreases the reference
value
7. FAN button: sets the fan speed
(3 levels + automatic)
8. Fan speed indicator (3 levels) +
automatic
9. DND indicator (red LED on: DO
NOT DISTURB)
10. Local contact
11. Connection to the BUS
Updated: 31/05/2018
CONTENTS
1. Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
2. Technical characteristics . . . . . . . . . . . . . . . . . .1
3. Standards, certifications and markings . . .1
4. Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
5. Connection diagrams . . . . . . . . . . . . . . . . . . . .2
6. Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
7. Configured version
Cat. No. 0 487 82/FL4663 . . . . . . . . . . . . . . . . .3
2. TECHNICAL CHARACTERISTICS
BUS/SCS power supply:
Consumption with screen off:
Consumption with ultra-bright screen:
Operating temperature:
Storage temperature:
Unit of measurement:
Loads controllable by an actuator:
Protection index:
Plate and surround colour (standard):
DEFAULT VALUES
Setting interval
Comfort
Economy
Frost guard
Thermal overload
3. STANDARDS, CERTIFICATIONS AND MARKINGS
EN 60669-2-5
CE marked
4. DIMENSIONS
129
Cat. No(s): 0 487 72/82
FL4653/53W/63
Page
18 - 27 VDC
8 mA
30 mA
0°C to +40°C
-20°C to +70°C
°C or °F
On/Off
Open/closed
Fan coil unit with 2 tubes and
On/Off valve
IP gateway (centralised HVAC
package)
Fan coil unit with 2 tubes and
proportional valve
Fan coil unit with 4 tubes and
On/Off valve
Fan coil unit with 4 tubes and
proportional valve
Proportional valve
Fan coil unit with 2 tubes and
proportional speed control
Fan coil unit with 4 tubes and
proportional speed control
IP 20, IK 04
Black Cat. No. 0 487 72/FL4653 or
White Cat. No. FL4653W
Heating
Air conditioning
3-40°C
3-40°C
21°C
25°C
18°C
28°C
7°C
35°C
42.4
11.5
Created: 24/04/2018
1/3

Advertisement

loading

Summary of Contents for LEGRAND bticino FL4653

  • Page 1 128, av. du Maréchal-de-Lattre-de-Tassigny - 87045 LIMOGES Cedex Tel: +33(0)5 55 06 87 87 Fax: +33(0)5 55 06 88 88 www.legrand.com Bedside panel Cat. No(s): 0 487 72/82 FL4653/53W/63 BUS-SCS CONTENTS Page 1. Description ......1 2.
  • Page 2 Bedside panel Cat. No(s): 0 487 72/82 FL4653/53W/63 BUS-SCS 5. CONNECTION DIAGRAMS Example of installation for hotel room (SCS installation) BUS power supply PRI: 220 – 240 V~ 185 – 175 mA MH201 HVAC 50/60 Hz SCS: 27 Vdc 600 mA actuator ART.
  • Page 3 - Hotel logo - Empty colour - Flush-mounted version The configurator is available on the following website: www.uxforupscalehotel.legrand.com. The list of pictogram and colour options (plate and surround) can be accessed via the configurator. Technical data sheet: S000102895EN-1 Updated: 31/05/2018...

This manual is also suitable for: