4. Louver control

4-1. Individual louver control(For Compact cassette type)

To independently can be set the airflow pattern of each louver as follows:
This function is given priority to overall louver control. But this function is release during the following
operation.
• Cold air prevention control
• Monitor mode on the auto change over operation
• Defrost operation
The air direction range will change as follows:
Use the wired remote controller to set this function. This function is only available by 2 wire remote
controller.
NOTE: When the 2 wire remote controller is disconnected, clear the individual setting. Otherwise,
this setting can't change.

4-2. All louver control(For Compact cassette type)

• All louver operation
When the mode is selected, the standard louver position of the each mode is set.
Cooling
Dry
Heating
Monitor
NOTES:
• Setting of the wireless remote controller is not displayed on the wired remote controller.
• The setting louver of the individual control function cannot be controlled.
4-1. Individual louver control(For Compact cassette type)
Operation mode
Standard Position
- (04-20) -
1
1
4
1
4. Louver control