Description

Rinnai Tankless Rack Systems (TRS) include wall mounted and free standing configurations. The wall mounted
rack systems are available for 2 or 3 water heaters. Free standing rack systems are available for 2, 3, 4, 5, or 6
water heaters.
The TRS can be ordered with Rinnai's Common Venting System, which consists of the CVent exhaust venting and
PP or PVC intake venting. Up to eight tankless units can share the same CVent system.
The Rinnai TRS features design details that make installation simple and straightforward.
Maneuverability: Fits, fully assembled, through standard 32-inch doorways and on elevators
Flexibility: Available in both wall-mount or freestanding design for indoor and outdoor installations.
Preassembled Gas and water manifolds are properly sized to maintain optimum performance.
The racks are constructed of powder-coated aluminum, powder coated steel, and stainless to stand up to the
most demanding commercial environments, while minimizing weight.
Optional electronic controls to obtain turn down ratios of up to 327:1 (Sold Separately).
NOTE: The TRS is designed to be used with Rinnai tankless water heaters only. Do not mount non-Rinnai water
heaters on the TRS.

Venting Options

Venting Options
Common Venting System ** PPtl, PPs
Concentric
Twin Pipe PVC/CPVC
Dual Pipe*
*This venting is provided by Centrotherm through their own distribution network
Refer to the water heater installation and operation manual for specific details regarding vent installation
option and installation.
Venting components are packaged separately from the pre-assembled Rack for field assembly of the vent
system by the contractor.
**Only the C199i is certified for both direct vent and exhaust only with room air (exhaust must terminate
vertically in room air application) when installed in a commercial common vent application only. Reference
Rinnai Common Vent (CVent) Manual for further information.
Exhaust Vent
Intake Vent
Material
Material
PVC, PPtl,
PPS
PPs
PVC
PVC/CPVC
PVC/CPVC
PPs
PPs or PVC
Max.
Diameter
Units
8"
8
100' (with 7 units) or 41' (with 8 units)
5"
1
4"
1
3"
1
3"
1
4
Max. Vent Length
Natural Gas
Propane
65'
100'
65'
41'
Rinnai Rack Installation
45'
65'
41'
41