Error Codes; Table 6-1: Error Codes - GE Kelman MINITRANS User Manual

Transformer oil dissolved gas and moisture monitor
Hide thumbs Also See for Kelman MINITRANS:
Table of Contents

Advertisement

6.2 Error Codes

A list of error codes that can appear on the LCD display panel and their meaning are
shown in Table 6—1.
NOTE: Error codes are offset by 1 from the Modbus register bit numbers.
Error code
Description
00
Missing mains input
01
PGA power supply voltage too low
02
PGA chopper frequency outside range
03
PGA IR-source outside range
04
Gas flow lower than limit
05
Background noise/vibration too high
06
Microphone test failed
07
Not level sensor 1 pulses (level)
08
Not level sensor 3 (drain)
09
Level sensor 1 (level)
10
Level sensor 2 (level alert)l
11
PGA Air temperature outside limits
12
Bad communication with control PCB
13
Gas leak test: Pump pressure too low
14
Gas leak test: Pressure decay too high
16
Oil temperature too low
17
Oil temperature too high
18
Oil pressure too low
19
Oil pressure too high
20
Oil pump tacho count too high
21
Oil pump pressure too low
22
Oil pump speed out of range
23
Manual oil sampling switch
24
Oil pump tacho count too low
25
{not used/defined}
26
5 V supply below 4.5 V
27
Temperature Sensor(s) 1 disconnected
28
Temperature Sensor(s) 2 disconnected
MA-006- MINITRANS User Guide - Rev 2.1
Table 6—1: Error codes
13-Oct-15