2 - ELECTRICAL CONNECTION

ATTENTION!
Electrical connections must be made by qualified personnel.
ATTENTION!
Electrical connection operations must be done with the system's power disconnected.
CH193VMC is connected directly to the Fantini Cosmi VMC machines. The connection changes based on the VMC code.
Note: For the correct installation of the CH193VMC / CH193BVMC panel:
1. Verify that power and data cables A and B are properly connected.
2. Data input A and B is polarized, make sure they are not reversed.
3. To avoid any electromagnetic disturbances, separate the signal
conductors (A, B, Vcc, GND and those for integration) from the power
ones using separate corrugated tubes at a distance of about 1.5m
from each other.
4. Use shielded and twisted cables, and ground them on the CH193VMC
side.
*Note: Jump the terminals.
AP20047 - AP20048 - AP20050 - AP20052 - AP20054 -
AP20056 - AP20058 - AP20064 - AP20066
Use a shielded cable and ground it on the CH193VMC side.