Electrical wiring of the infrared flame detection probe.
It is important to achieve practically disturbance- and loss-free
signal transmission:
Never run the detector cables together with other cables:
– Line capacitance reduces the magnitude of the flame signal.
– Use a separate cable.
Technical data
LMV51... basic unit
Mains voltage
Mains frequency
Power consumption
Safety class
Terminal loading
Unit fuse F1 (internally)
'Inputs'
Perm. mains primary fuse (externally)
Undervoltage
• Safety shutdown from operating position
at mains voltage
• Restart on rise in mains voltage
Oil pump / magnetic clutch (nominal voltage)
• Nominal current
• Output factor
Air pressure switch test valve (nominal voltage)
• Nominal current
• Output factor
Terminal loading
Total contact loading:
'
'
• Mains voltage
Outputs
• Input current of unit (safety loop) total
load on contacts resulting from:
- Fan motor contactor
- Ignition transformer
- Valve
- Oil pump / magnetic clutch
Single contact loading:
Fan motor contactor (nominal voltage)
• Nominal current
• Output factor
Alarm output (nominal voltage)
• Nominal current
• Output factor
Ignition transformer (nominal voltage)
• Nominal current
• Output factor
Fuel valve gas (nominal voltage)
• Nominal current
• Output factor
Fuel valve oil (nominal voltage)
• Nominal current
• Output factor
Cable lengths
Main line
Operation
Environmental
conditions
Climatic conditions
Mechanical conditions
Temperature range
Humidity
20027770
Technical description of the burner
14
GB
Observe the permissible cable lengths.
The detection probe is not protected against electrocution
risks and must be protected against accidental contact.
Place the detection probe so that it is correctly installed and
the flame is correctly detected.
AC 230 V -15 % / +10 %
50 / 60 Hz ±6 %
< 30 W (typically)
I, with parts according to II and III to DIN EN 60730-1
6.3 AT
Max. 16 AT
< AC 186 V
> AC 188 V
2A
cos  > 0.4
0.5A
cos  > 0.4
AC 230 V -15 % / +10 %
Max. 5 A
1A
cos  > 0.4
1A
cos  > 0.4
2A
cos  > 0.2
2A
cos  > 0.4
1A
cos  > 0.4
Max. 100 m (100 pF/m)
DIN EN 60721-3-3
class 3K3
class 3M3
-20...+60 °C
< 95 % r.h.