Download Print this page

Daikin RXF125KC Removal Procedure page 28

2.5/3.5 kw class

Advertisement

Removal of Compressor
Step
3
Heat up the brazed part
of the suction side and
disconnect.
Lift the compressor up
4
and remove it.
26
Procedure
Suction side
Points
Note:
Do not use a metal saw for
cutting pipes by all means
because the sawdust comes
into the circuit.
When withdrawing the pipes,
be careful not to pinch them
firmly with pliers. The pipes
may get deformed.
Provide a protective sheet or
a steel plate so that the
brazing flame cannot
(R12032)
influence peripheries.
Be careful so as not to burn
the compressor terminals,
the name plate, the heat
exchanger fins.
(R7254)
Removal Procedure
Si001157

Advertisement

loading

This manual is also suitable for:

Rxf135kcRzs235kcRzs235kcgRzs235kcpRzs235kcs