Download Print this page

Daikin RXF125KC Removal Procedure page 25

2.5/3.5 kw class

Advertisement

Si001157
Step
4
Remove the screw and
remove the four way
valve coil.
5
Remove the putty.
Before working, make
sure that the refrigerant
gas is empty in the circuit.
Be sure to apply nitrogen
replacement when
heating up the brazed
part.
6
Heat up the brazed
parts and withdraw the
piping with pliers.
Removal Procedure
Procedure
Four way valve coil
Putty
Four way valve
Removal of Four Way Valve
Points
Warning
Be careful not to get yourself
burnt with the pipes and other
parts that are heated by the
gas brazing machine.
Warning
If the refrigerant gas leaks
during work, ventilate the
room. (If the refrigerant gas is
exposed to flames, toxic gas
may be generated.)
Caution
From the viewpoint of global
(R7247)
environment protection, do
not discharge the refrigerant
gas in the atmosphere. Make
sure to collect all the
refrigerant gas.
Cautions for restoration
1. Restore the piping by non-
oxidation brazing.
2. It is required to prevent the
carbonization of the oil inside
the four way valve and the
deterioration of the gaskets
affected by heat. (Keep
below 120°C.) For the sake
(R7248)
of this, wrap the four way
valve with wet cloth and
provide water so that the
cloth does not dry.
In case of difficulty with gas
brazing machine
1. Disconnect the brazed part
where is easy to disconnect
and restore.
2. Cut pipes on the main unit
with a tube cutter in order to
make it easy to disconnect.
(R7249)
23

Advertisement

loading

This manual is also suitable for:

Rxf135kcRzs235kcRzs235kcgRzs235kcpRzs235kcs