Download Print this page

Toshiba TOSVERT VF-A5 Series Option Manual page 16

High performance inverter
Hide thumbs Also See for TOSVERT VF-A5 Series:

Advertisement

TOSHIBA
E6580704
When a binary data write. input switch is being used, set [
11::]
(input terminal
selection) under
[Gr.SI::]
to [
I]
(individual setting).
Setting [
11::]
(input terminal selection) under
[Gr. 51::]
to [ I] (individual setting)
enables the
~
and
\l
keys on the panel to be used to read out parameters
[ 11: D] (input terminal 0 (R) function selection) through [
/I:
I I] (input terminal 11
virtual terminal function).
Parameters [
/I:
D] (input terminal 0 (R) function) through [
/I:
I I] (input terminal
11 virtual terminal function) correspond to the inverter terminals as described
below:
Inverter standard
LED display code _ Function and
d~fault
setting
terminal name
R
[ 11: D]
[D]
(Reverse operation)
S1
[ /I: /]
[
/]
(SS 1: 15-step multispeed operation)
S2
[ 11:
2]
[2]
(SS2:15-step multispeed operation)
S3
[ /I: 3]
[ 3]
(SS3: 15-step multispeed operation)
S4
[ /I: Y]
[ Y]
(SS4: 15-step multispeed operation)
F
[ /I: 5]
[ 5]
(Forward operation)
RES
[ /I: 6]
[6]
(Failure reset)
ST
[ /I: '1]
[ '1]
(Gate ON/OFF)
S5
[ /I:
8]
[ 8]
(Change JOG)
S6
[ /I:
9]
[ 9]
(Change AD2)
S7
[ / I:
I
0]
[ I
0] (Emergency stop)
Virtual terminal
[ /I:
I I]
[ 3
3] (Uncontrolled)
(normally closed)
Unused terminals from [
/I:
0] to [
/I:
I I] are set to [ Y 2] (write binary data).
3.
Set [DP
I:]
(optional board selection) under
[Cr .I: r]
to [ 6] (3-digit BCD input in
1 Hz increments).
4.
The inverter's frequency command can now be set according to the following
equation:
j
Frequency Command = BCD data
x
1 (Hz) .
-
13
-

Advertisement

loading

This manual is also suitable for:

Tosvert vf5x-4526a