Note:
This option is not available on X2 base.
3.5.3
The iX Developer project and all the files needed to run the application are copied
to an external USB flash drive or other USB connected storage device. Make sure
that the storage device is connected before trying this option.
3.5.4
The iX Developer project and all its corresponding files are deleted from the
operator panel. There is no way of undeleting a project, make sure that the project
should be deleted before confirming the deletion.
3.5.5
The operator panel image can be restored to the panel image version the operator
panel was using, before a new panel image was loaded into the operator panel.
This option is used to restore a panel to a known working condition.
Note:
This option is only available on X2 panels, with the exception of X2 base
Note:
If the operator panel contains a CODESYS Runtime, then the CODESYS Runtime must be
downloaded once again to the panel after the panel image has been changed.
3.5.6
The operator panel image can be restored to the panel image version that the
operator panel was shipped with from the factory. Use this option if all else fails,
this will downgrade the operator panel to its initial state.
Beijer Electronics, MAEN205G
Copy project to USB
Delete project
Restore panel to previous image
Restore panel to factory image
Service menu