Download Print this page

Outer Panels - Daikin RKV50NRV16 Service Manual

Removal procedure

Advertisement

Outer Panels

1. Outer Panels
Warning
Step
1
Remove the 4 screws
and remove the top
panel.
2
Remove the 9 screws
of the front panel.
3
Unfasten the right side
hooks and remove the
front panel.
4
Remove the screw and
remove the discharge
grille.
2
Be sure to wait for 10 minutes or more after turning off all power supplies before
disassembling work.
Procedure
Front panel
Discharge grille
Projection (rear side)
Top panel
(R19515)
The discharge grille has 2
projections to prevent its
rotation. Press the projection
from the rear side and rotate
(R19429)
the discharge grille to
remove it.
Si001355E
Points
rear side
(R19405)