Operating and Maintenance Instructions
Introduction
Commercial Dual Fan Controller, mains powered with enclosure, controls two fans Stop/Run and Low/High
speed. Speeds preset by on-board trimmers, selected by 230VAC and volt-free inputs. Optional alternate fan run
with selectable duty (changeover) period, or simultaneous (Load Share) and Single Fan operation.
With LED indicators and alarm output. Configurable options set by on-board DIP switches.
Specification
Supply Voltage
AC line Frequency
Supply Current
Alarm Relay Contacts
Operating Environment
Connection Details (see "Terminal Block Use" below")
Mains Connector J1
Pin
Function
SL1
1
Switched Live 1, Low/High fan speed Select input
2
Switched Live 2, Stop/Run control input (shipped with link to 230VAC Live to Run)
SL2
L
3
230VAC, Live (for Stop/Run control link)
L
4
230VAC, Live (Supply to Fan 1)
L
5
230VAC, Live (Input)
L
6
230VAC, Live (Supply to Fan 2)
N
7
230VAC, Neutral (spare)
N
8
230VAC, Neutral (Supply to Fan 1)
N
9
230VAC, Neutral (Input)
N
10
230VAC, Neutral (Supply to Fan 2)
E
11
Earth (Supply to Fan 1)
E
12
Earth (Input)
E
13
Earth (Supply to Fan 2)
E
14
Earth (spare)
Control Connector J2
Pin
Function
1
Alarm Relay, Contact A (Contacts Closed = No Alarm)
2
Alarm Relay, Contact B
3
Fan 1 Speed Control PWM Output
4
Fan 1 Tachometer Open Collector / Relay Input
5
Fan 1 GND / 0V
6
Fan 2 Speed Control PWM Output
7
Fan 2 Tachometer Open Collector / Relay Input
8
Fan 2 GND / 0V
9
BMS Low/High fan speed Select Input, Volt Free Contacts
10
0V for BMS input
11
Stop/Run control input, Volt Free Contacts (shipped with link to 0V to Run)
12
0V for Stop/Run input
13
Remote Low/High fan speed Select Input, Volt Free Contacts
14
0V for Remote Low/High input
Note: all "0V" terminals on J2 are commoned.
Fan Compatibility
Fan Speed control outputs compatible with EC 0-10V or Open Collector PWM speed controlled fans, 2kHz PWM,
maximum of 12 EC Fans per 0-10V output.
Tachometer / Relay input compatible with Open Collector tachometer or Relay Alarm fans.
210-OMI12492_Iss3.doc
V AC
Hz
A
Controller 15mA, plus Fans if wired via PCB 13A max.
ORIGINAL INSTRUCTIONS
ebm-papst UK Ltd
Chelmsford Business Park Chelmsford Essex CM2 5EZ
Telephone: +44(0)1245468555 Fax: +44(0)1245466336
e-mail
sales@uk.ebmpapst.com
CN1082
207 – 253 VAC
47 – 63 Hz
100mA max, 60VDC max
-30 to 60°C, IP66 Enclosure
Fan
1
Fan
2
Page 2 of 7