Gree GMV5 Series Manual page 113

Heat recovery vrf units
Hide thumbs Also See for GMV5 Series:
Table of Contents

Advertisement

GMV5 HR HEAT RECOVERY VRF Units Technical Sales Guide
Notes for correction of the long connection pipe:
a. The above connection of long connection pipe indicates the maximum capacity under the standard
indoor unit capacity configuration.
b. Set out below are some load configurations:
Maximum system capacity: the smaller one of the indoor unit capacity and the maximum outdoor unit
capacity (two algorithms are provided below)
When the configuration ratio of indoor unit is less than 100%
Maximum outdoor unit capacity = Capacity when the configuration ratio is 100% in the outdoor unit
capacity correction table × Long connection pipe correction coefficient of the longest indoor unit
distance
When the configuration ratio of indoor unit reaches 100%
Maximum outdoor unit capacity = Capacity of the corresponding configuration ratio in the outdoor
unit capacity correction table × Long connection pipe correction coefficient of the longest indoor unit
distance.