Troubleshooting
approximately 30 seconds, turn the "Mode" selection switch
to the desired mode, i.e. Heat, Cool or Auto.
Method 2
To reset the system at the unit, cycle the unit power by
turning the disconnect switch "Off" and then "On".
Condensate Overflow Switch
When the condensate overflow switch is closed, a drain
pan overflow condition is indicated and it will shut unit
operations down.
Unit Economizer Control (ECA)
Verify Economizer Status by Economizer Actuator (ECA)
LED indicator:
•
OFF: No Power or Failure
•
ON: Normal, OK to Economize
34
•
Slow Flash: Normal, Not OK to Economize
•
Fast Flash - 1/4 Second On / 2 Seconds Off:
–
Error Code: Communications Failure
•
Pulse Flash: 1/30 Second On / 1/4 Second Off: (2
Seconds between pulse sequences)
Error Code
•
1 Flash: Actuator Fault
•
2 Flashes: CO
Sensor
2
•
3 Flashes: RA Humidity Sensor
•
4 Flashes: RA Temp Sensor
•
6 Flashes: OA Humidity Sensor
•
7 Flashes: OA Temp Sensor
•
8 Flashes: MA Temp Sensor
•
9 Flashes: On-board Setpoint Failure
RT-SVX058G-EN