Fujitsu ABYG54KRTA Service Manual page 148

Ceiling type air conditioner
Table of Contents

Advertisement

 When function setting is "Forced stop" mode
• In the case of "Edge" input
Function
setting /
46-02
• In the case of "Pulse" input
Function
setting /
46-02
Input 1
Input 2
Indoor unit
Remote controller
NOTES:
• When the forced stop is triggered, indoor unit stops and Operation/Stop operation by the re-
mote controller is restricted.
• When forced stop function is used with forming a remote controller group, connect the same
equipment to each indoor unit within the group.
3-4. Details of function
Rotary SW of
External input and
output PCB
-
Input of indoor unit
External input and
60-00 / 1
On
Input
Off
Forced stop
Normal
Operation
Indoor unit
Stop
Remote controller
Rotary SW of
External input and
output PCB
External input and
60-00 / 1
On
Off
On
Off
Forced stop
Normal
Operation
Stop
External input
Terminal
Input 1
output PCB
On
External input
Input 1
output PCB
Input 2
On
- (05-16) -
Input signal
Command
Off → On
Forced stop
On → Off
Normal
Off → On
Forced stop
On → Off
Normal
On
On
Input signal
Command
Pulse
Forced stop
Pulse
Normal
On
On
3. External input and output for indoor unit