Types, Measured Temperature Ranges And Data Resolutions Of Usable Thermocouples - Mitsubishi MELSEC-Q Q64TCTT User Manual

Table of Contents

Advertisement

2.2 Types, Measured Temperature Ranges and Data Resolutions of Usable
Thermocouples
Thermocouple
Measured
Type
temperature range
R
0 to 1700
0 to 500
0 to 800
0 to 1300
K
-200.0 to 400.0
0.0 to 400.0
0.0 to 500.0
0.0 to 800.0
0 to 500
0 to 800
0 to 1200
J
0.0 to 400.0
0.0 to 500.0
0.0 to 800.0
-200 to 400
-200 to 200
0 to 200
T
0 to 400
-200.0 to 400.0
0.0 to 400.0
S
0 to 1700
B
0 to 1800
0 to 400
0 to 1000
E
0.0 to 700.0
N
0 to 1300
0 to 400
U
-200 to 200
0.0 to 600.0
0 to 400
0 to 900
L
0.0 to 400.0
0.0 to 900.0
PL II
0 to 1200
W5Re/W26Re
0 to 2300
°C
Data resolution
1
1
0.1
1
0.1
1
0.1
1
1
1
0.1
1
1
0.1
1
0.1
1
1
3
°F
Measured
temperature range
0 to 3000
0 to 1000
0 to 2400
0.0 to 1000.0
0 to 1000
0 to 1600
0 to 2100
0.0 to 1000.0
0 to 700
-300 to 400
0.0 to 700.0
0 to 3000
0 to 3000
0 to 1800
———
0 to 2300
0 to 700
-300 to 400
———
0 to 800
0 to 1600
———
0 to 2300
0 to 3000
Data resolution
1
1
0.1
1
0.1
1
0.1
1
1
1
———
1
1
———
1
———
1
1

Advertisement