Item
Output signal
Rated load voltage
Max. load current
Max. inrush current
Transistor
OFF-time leakage
output
current
ON-time max.
voltage drop
Response time
Insulation system
Dielectric withstand voltage
Insulation resistance
Heater wire
Current sensor*1
break
detection
specificatios
Input accuracy
Alarm delay count
Number of occupied I/O points*2
Connection terminals
Applicable wire size (mm)
Applicable crimping terminals
Internal current consumption (A)
Weight (kg)
Outline dimensions (mm)
*1 : Only the current sensor of URD Co., Ltd. may be used.
*2 : When using the Q64TCTTBW, the device numbers of the I/O signals are
incremented by 16 points due to the empty points of the left-hand side slot.
In this manual, therefore, read the I/O signals as indicated below
depending on the module used.
Example) When the signal is indicated as Yn1
When using Q64TCTT: Y1
*3 : For the noise immunity, withstand voltage, insulation resistance and others
in the PLC system using this module, refer to the power supply module
specifications given in the used CPU module user's manual.
Q64TCTT
0.1A/1 point 0.4A/common
DC1.0V(TYP) 0.1A
OFF∏ ON: 2ms max.
Across input and earth
Across input and channel : Transformer insulation
Across input and earth
Across input and channel : 500VAC for 1 minute
Across input and earth
Across input and channel : 500VDC 20M
———
16 points/1 slot
(I/O assignment:
16 intelligent points)
18-point terminal block
R1.25-3,1.25-YS3,RAV1.25-3,V1.25-YS3A
0.55
0.20
27.4 (W) × 98 (H) × 112 (D)
When using Q64TCTTBW: Y11
2
Specifications
Q64TCTTBW
ON/OFF pulse
DC10 to 30V
0.4A 10ms
0.1mA max.
DC2.5V(MAX) 0.1A
ON∏ OFF: 2ms max.
: Transformer insulation
: 500VAC for 1 minute
: 500VDC 20M
or more
or more
The following current sensor
made by URD Co., Ltd.
Input accuracy
CTL-12-S36-8(0.0 to 100.0A)
CTL-6-P-H(0.00 to 20.00A)
Input range width × (±1.0%)
3 to 255
32 points/2 slots
(Default I/O assignment:
16 empty points + 16 intelligent
points)
18-point terminal block ×2
0.3 to 0.75
0.64
0.30
55.2 (W) × 98 (H) × 112 (D)