Advertisement

Quick Links

Temperature Control Module
MITSUBISHI
General-Purpose PROGRAMMABLE LOGIC CONTROLLER
Thank you for purchasing the Mitsubishi general-purpose
programmable logic controller MELSEC-Q series.
Prior to use, please read this manual thoroughly and
familiarize yourself with the product
© 2000 MITSUBISHI ELECTRIC CORPORATION
User's Manual
MODEL
Q64TCTT-U-H-JE
MODEL
CODE
IB(NA)-0800120-B(0603)MEE
(Hardware)
Q64TCTT
Q64TCTTBW
13JQ97

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi MELSEC-Q Q64TCTT

  • Page 1 Temperature Control Module MITSUBISHI General-Purpose PROGRAMMABLE LOGIC CONTROLLER User’s Manual (Hardware) Q64TCTT Q64TCTTBW Thank you for purchasing the Mitsubishi general-purpose programmable logic controller MELSEC-Q series. Prior to use, please read this manual thoroughly and familiarize yourself with the product MODEL Q64TCTT-U-H-JE MODEL...
  • Page 2 SAFETY PRECAUTIONS (Read these precautions before using.) When using Mitsubishi equipment, thoroughly read this manual and the associated manuals introduced in this manual. Also pay careful attention to safety and handle the module properly. These SAFETY PRECAUTIONS classify the safety precautions into two categories: “DANGER”...
  • Page 3 [INSTALLATION PRECAUTIONS] CAUTION Use the PLC in an environment that meets the general specifications contained in the CPU user's manual. Using this PLC in an environment outside the range of the general specifications may cause electric shock, fire, malfunction, and damage to or deterioration of the product.
  • Page 4: Revisions

    Chapter 3, 4 This manual confers no industrial property rights or any rights of any other kind, nor dose it confer any patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.
  • Page 5: Table Of Contents

    (details) Conformance to the EMC Directive/Low Voltage Directive When incorporating a Mitsubishi PLC that is compliant with the EMC and low voltage directives into any other product and ensuring compliance with these directives, refer to Chapter 3 "EMC and Low Voltage Directives" of the User's Manual (Hardware) for the PLC CPU included with the CPU module or base unit.
  • Page 6: Overview

    1. OVERVIEW This user's manual provides the specifications, handling, part names and others of the following temperature control modules used with the MELSEC-Q series CPU modules. Q64TCTT temperature control module • Q64TCTTBW temperature control module with wire break detection feature •...
  • Page 7 Specifications Item Q64TCTT Q64TCTTBW Output signal ON/OFF pulse Rated load voltage DC10 to 30V Max. load current 0.1A/1 point 0.4A/common Max. inrush current 0.4A 10ms Transistor OFF-time leakage output 0.1mA max. current ON-time max. DC1.0V(TYP) 0.1A DC2.5V(MAX) 0.1A voltage drop Response time OFF∏...
  • Page 8: Types, Measured Temperature Ranges And Data Resolutions Of Usable Thermocouples

    2.2 Types, Measured Temperature Ranges and Data Resolutions of Usable Thermocouples °C °F Thermocouple Measured Measured Type Data resolution Data resolution temperature range temperature range 0 to 1700 0 to 3000 0 to 500 0 to 1000 0 to 800 0 to 2400 0 to 1300 -200.0 to 400.0...
  • Page 9: Loading And Installation

    3. LOADING AND INSTALLATION 3.1 Handling Instructions There are the following instructions for handling the Q64TCTT(BW). (1) Do not drop the case and connectors of the module and subject them to hard impact. (2) Tighten the mounting and terminal screws of the module within the following ranges.
  • Page 10: Names And Settings Of The Parts

    4. NAMES AND SETTINGS OF THE PARTS Q64TCTT Q64TCTTBW ERR. ERR. Number Name and Appearance Description Indicates the operating status of the Q64TCTT(BW). : Operating normally. : 5V power switched off, a watchdog timer error RUN LED occurred, or a CPU stop error occurred when the intelligent function module switches of all channels are set to "CLEAR".
  • Page 11 (1) When using Q64TCTT Terminal Number Signal Name COM- Reserved CH1+ CH2+ CH1- CH2- Reserved Reserved CH3+ CH4+ CH3- CH4- (2) When using Q64TCTTBW Terminal Number Signal Name Reserved CT1+ CT1- CT2+ CT2- COM- CT3+ Reserved CT3- CH1+ CT4+ CH2+ CT4- CH1- CT5+...
  • Page 12: Wiring

    5. WIRING 5.1 Wiring Instructions (1) Use separate cables for the AC control circuit and Q64TCTT(BW)'s external input signals to avoid the influence of AC side surges and inductions. (2) Do not run the module cables near, or bundle them with, the main circuit and high-voltage cables and the load cables from other than the PLC.
  • Page 13 (2) When using Q64TCTTBW Q64TCTTBW Current sensor (CT) DC24V Controlled object Connector Connector CT input circuit *: Always use shielded wires for cables. POINT When using the heater wire break detection feature, you need to make CT input channel assignment setting. In the above wiring example, as CT1 is used with the loop of channel 1, set 1 (channel 1) to the channel assignment setting buffer memory (108H) of CT1.
  • Page 14: Setting From Gppw

    6. SETTING FROM GPPW The Q64TCTT(BW) allows you to set the output status at an error stop of the PLC CPU by making the intelligent function module switch setting. Make the intelligent function module switch setting using the I/O assignment setting of GPPW.
  • Page 15: Outline Drawings

    7. OUTLINE DRAWINGS (1) Q64TCTT Q64TCTT ERR. 2 (0.08) 112 (4.41) 27.4 (1.08) Unit: mm (inch) (2) Q64TCTTBW Q64TCTTBW ERR. 2 (0.08) 112 (4.41) 55.2 (2.17) Unit: mm (inch)
  • Page 16 Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi products; damage, secondary damage, accident compensation caused by special factors unpredictable by Mitsubishi;...