INSTRUCTION MANUAL
LIGHTNING SURGE PROTECTOR FOR POWER SUPPLY USE

BEFORE USE ....

Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
Lightning surge protector ...................................................(1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTALLATION / INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, and basic main-
tenance procedure.
LIMITATION APPLICABLE TO M-RESTER
The M-RESTER will protect electronics equipment from
damage caused by lightning by absorbing most of the
surge voltages.
However, M-RESTER may not be effective against cer-
tain extremely high voltages caused by a direct or almost
direct hit by lightning.
M-RESTER must be installed according to this installa-
tion / instruction manual.
GENERALS
■ FUNCTION & FEATURES
Designed for installation where AC power enters the con-
trol panel for relatively large power consuming equipment
such as large instrumentation panels, computer systems or
telemetering systems in central control rooms or operation
centers
■ SPECIFICATIONS
BETWEEN LINES
MH-1201
Discharge voltage
190V min. 380V min.
(p-p)
Max. surge voltage* 350V max. 700V max.
Leakage current
≤1A including relay coil
current at rated voltage
Response time
Discharge current
Max. load current
Voltage drop
Rated line voltage
100V/110V/120V AC (MH-1201)
200V/220V/240V AC (MH-2201/2203)
*The maximum voltage that could pass through M-RESTER.
Protected equipment must be able to withstand this voltage
for a very short time period.
(200A)
LINE TO GND
MH-2201/2203
410V min.
700V max.
≤1mA
@150V DC
(MH-1201)
@300V DC
(MH-2201/2203)
≤0.1 µsec
10000A (8 / 20 µsec.)
200A
≤2V (50/60 Hz)
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
MODEL

POINTS OF CAUTION

■ ENVIRONMENT
• When heavy dust or metal particles are present in the at-
mosphere, install M-RESTER inside proper housing and
ventilate it.
• Do not install the M-RESTER where it is subjected to
continuous vibration. Do not apply physical impact to the
M-RESTER.
• Environmental temperature must be within -5 to +55°C
with a relative humidity within 30 to 90% RH in order to
ensure adequate life span and operation.
■ DIELECTRIC STRENGTH TEST
• The MH starts discharging at 410V or more voltage ap-
plied across power supply terminals and metallic hous-
ing. DO NOT conduct a dielectric strength test with the
MH connected to a power source.
• For confirming insulation of the unit, conduct the dielec-
tric strength test WITH ALL WIRES REMOVED, or con-
duct an insulation resistance test (@250V DC).
■ RATED CURRENT
• Be sure that the rated current of protected equipment
does not exceed the maximum load current specification
of the M-RESTER.
• Be sure to install a breaker which matches the current
rating at the power source side of the M-RESTER.
■ AND ....
We recommend that you keep spare M-RESTERs so that
you can replace them when necessary.

COMPONENT IDENTIFICATION

Power Pilot Lamp
MH-1201
MH-2201
MH-2203
Grommet with Film
Body
Nameplate
EM-8181 Rev.6 P. 1 / 4

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MH-1201 and is the answer not in the manual?

Questions and answers

Summary of Contents for M-system MH-1201

  • Page 1 (200A) MH-2203 BEFORE USE ..POINTS OF CAUTION Thank you for choosing M-System. Before use, please check ■ ENVIRONMENT contents of the package you received as outlined below. • When heavy dust or metal particles are present in the at-...
  • Page 2 MH-1201 / MH-2201 / MH-2203 INSTALLATION Refer to the drawings below. ■ EXTERNAL DIMENSIONS mm (inch) 300 (11.81) 250 (9.84) 250 (9.84) 6 (.24) 4–8.5 (.33) dia. MTG HOLE GROMMET WITH FILM SG–32A 50 (1.97) 50 (1.97) 135 (5.31) (32 mm or 1.26" dia.)