Page 1
FIELD DEVICE CONNECTIONS The gateway can connect with up to 8 boilers. Please see job specific Riello burner drawings for linkageless LMV3, LMV5 burners. ARRAY 1.0 Integration *** RS232 Converter with Array 1.0 is 20147499 (1 per boiler) *** RS232-RS485 Device on Array V1.0 is pow-...
Page 2
CONDEXA LOW VOLTAGE TERMINAL STRIP (TB1) *** AL Bus for cascade control is on a separate daisy chain. Please see Condexa Installation and Operation Manual RIELLO CONTROLLER MODBUS RTU SET-UP CONTROLLER SET UP TABLE - FROM GATEWAY TO RIELLO DEVICE CONTROLLER ADDRESSING BAUD RATE PARITY...
Page 3
- all BAS side configurations are done from the touch- screen. Dip switches are ignored, except for S3 which must be in the “off ” position. - Please consult automation manuals for more details. B Dipswitches - SELECT PROFILE (ONLY N35 GATEWAY) Profile LMV3 LMV5...
Page 4
2. If “ERR” LED light is flashing red, ensure dipswitch A7 is in the off position. To reset gateway move the S3 dipswitch to the “off ” position, then back to the “on” position. RIELLO BURNERS NORTH AMERICA 35 Pond Park Road 2165 Meadowpine Blvd.