G4106 (Module Driver v4.7)
Technical Instructions
Introduction .................................................................................................. 2
Specifications ............................................................................................... 2
Mounting ....................................................................................................... 2
Addressing and Baud Rates ........................................................................ 3
Setting the Address ............................................................................... 3
Setting the CMnet Baud Rate ............................................................... 3
Power Wiring ............................................................................................... 3
Communications Wiring .............................................................................. 4
Universal Inputs ........................................................................................... 4
Procedure .............................................................................................. 5
Custom Translation Tables ......................................................................... 7
Procedure .............................................................................................. 7
Digital Outputs .............................................................................................. 8
Procedure .............................................................................................. 8
Manual Operation ................................................................................. 8
Analog Outputs ............................................................................................ 8
Procedure .............................................................................................. 8
Downloading Memory ................................................................................. 9
LEDs .............................................................................................................. 9
LED Identification .................................................................................. 9
LED Power-up Sequence ...................................................................... 9
Checkout & Troubleshooting .................................................................... 10
Manually Formatting the Module ............................................................. 10
Fuses ........................................................................................................... 11
Production Date ......................................................................................... 11
Module Driver ............................................................................................. 12
Parameter Page .................................................................................. 12
Status Page .......................................................................................... 12
Channel Numbers ...................................................................................... 13
Rev (29-AUG-97) • Module Driver v4.7
Contents
1
© 1995-97 Automated Logic Corporation

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the G4106 and is the answer not in the manual?

Questions and answers

Summary of Contents for Automated Logic G4106

  • Page 1: Table Of Contents

    G4106 (Module Driver v4.7) Technical Instructions Contents Introduction ....................2 Specifications ....................2 Mounting ....................... 2 Addressing and Baud Rates ................ 3 Setting the Address ................3 Setting the CMnet Baud Rate ............... 3 Power Wiring ....................3 Communications Wiring ................4 Universal Inputs ...................
  • Page 2: Introduction

    Power: 24 VAC ±10%, 50-60 Hz, 25VA power Mounting consumption. Mount the G4106 in a panel using the four holes provided Protection: Built-in surge and transient protection on the cover plate. Be sure to leave about 2 inches on circuitry. Optically isolated communications.
  • Page 3: Addressing And Baud Rates

    15 VA in order to properly drive the modules under all circumstances. Measuring the Set the G4106's address and baud rate using the voltage level at the power terminals is not an accurate 8-position dip switch (see Figure 1 for location).
  • Page 4: Communications Wiring

    Universal Inputs a voltmeter. A total of 200mA is supplied to these inputs for 4-20mA Turn the G4106's power switch ON and verify that the transducer wiring. If the total current required by all of the module powers up properly.
  • Page 5: Procedure

    Figure 4. module. Turn the G4106's power switch ON. Dry Contact: 0.5 mA maximum sense current. Some current switches that are not true dry contact closures may not go to zero ohms when the switch is closed.
  • Page 6 Figure 6: I/O Wiring Rev (29-AUG-97) • Module Driver v4.7 © 1995-97 Automated Logic Corporation...
  • Page 7: Custom Translation Tables

    Provided on the parameter page of the NOTE: The lowest resistance range allowed on a G4106 module driver (see Figure 14) are two user slidepot input is 5k Ohms. This guarantees that sufficient definable tables for translating these inputs.
  • Page 8: Digital Outputs

    Digital Outputs Current Mode (4-20 mA): The G4106 provides four digital outputs which are wired While the G4106's analog outputs are designed to output as shown as shown in Figures 5 and 6. These outputs are voltage, it is possible to use these outputs to drive current described as follows: 24 VAC or VDC maximum, each mode devices.
  • Page 9: Downloading Memory

    Transmit - lights when the G4106 transmits data over the Downloading Memory CMnet. Use the following procedure to download memory into the Receive - lights when the G4106 receives data from the GX-Line modules. If you have any problems during this CMnet.
  • Page 10: Checkout & Troubleshooting

    Turn the G4106's power switch OFF. this in NetScan, issue the NU command and enter Set all eight of the G4106's address and baud rate dip "DNx4"(where "x" equals the COM port number for switches to the ON position (see Figure 1 for connection) before connecting.
  • Page 11: Fuses

    Fuses Production Date The G4106 is protected by two 0.5 A pico fuses on the The production date of the module can be determined by a CMnet (+) and (-) terminals, and by one 3.0 A pico fuse on sticker on the back of the module. The first three the 24 VAC power terminal.
  • Page 12: Module Driver

    T r e n d i n g I n f o r m a t i o n : Chan Trending Interval Samples — —— —— ———— ———— ——— Rev (29-AUG-97) • Module Driver v4.7 © 1995-97 Automated Logic Corporation...
  • Page 13: Channel Numbers

    † Degrees Celsius can only be displayed in SVW 1.1 or later when the GFB is made in Eikon 2.0 or later with the "METRIC=TRUE" command set in the alc.ini file. Rev (29-AUG-97) • Module Driver v4.7 © 1995-97 Automated Logic Corporation...