Technical Instructions
InterOP8500
LEDs 18
Automated Logic Corporation • 1150 Roberts Blvd. • Kennesaw, GA 30144 • 770/429-3000 • 770/429-3001 Fax •
www.automatedlogic.com • Copyright 2001 Automated Logic Corporation. All rights reserved. Automated Logic, the
Automated Logic logo, SuperVision, Eikon, Alert, and InterOp are registered trademarks of Automated Logic
Corporation. WebCTRL is a trademark of Automated Logic Corporation. BACnet
All other brand and product names are trademarked by their respective companies.
®
is a registered trademark of ASHRAE.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the InterOP8500 and is the answer not in the manual?

Questions and answers

Summary of Contents for Automated Logic InterOP8500

  • Page 1: Table Of Contents

    Production Date 19 Sample GFB 20 Automated Logic Corporation • 1150 Roberts Blvd. • Kennesaw, GA 30144 • 770/429-3000 • 770/429-3001 Fax • www.automatedlogic.com • Copyright 2001 Automated Logic Corporation. All rights reserved. Automated Logic, the Automated Logic logo, SuperVision, Eikon, Alert, and InterOp are registered trademarks of Automated Logic ®...
  • Page 2: Introduction

    12VDC power supply for its Introduction binary outputs. The InterOP8500 board The InterOP8500 mounts directly to a Johnson contains the microprocessor, a connection Controls panel, replacing the Johnson FIC-1n1 port for the network connection, and a port control board and the PCR-102.
  • Page 3: Specifications

    The table below outlines the limitations and Specifications requirements depending on whether you are Power 5VDC, 175mA (external), 275 mA using WebCTRL or SuperVision to (internal). communicate with your InterOP8500. 12VDC, 25mA. 12VDC, 175mA (external power), 25 mA WebCTRL SuperVision (internal power) supplied through the...
  • Page 4: Mounting

    Memory 1MB Flash memory, 2MB non- Up to five expansion Mx modules can be volatile battery-backed RAM (which connected to an InterOP8500. The stack can stores data even during power failures). be arranged in a single column using the 128 bytes of EEPROM.
  • Page 5: Power Wiring

    Termination Board (FTB-102) Edge Connectors to External Power Supply Figure 3. InterOp8500/PWRSUP8500 mounted in Johnson Controls panel Whenever possible, make sure the module's 10's power and communications connections are working properly before connecting any inputs and outputs. Care should be taken to isolate power wiring from all other wiring inside the enclosure.
  • Page 6: Using The Alc Power Supply

    Power Adapter Cable to External Power Supply Figure 5. InterOp8500/RPA-105 and LPS-105 mounted in Johnson Controls panel Using the ALC Power Supply The PWRSUP8500 power supply replaces both 4. Take out the mounting screw from the the Johnson Controls LPS-105 and Johnson face of the LPS-105 and remove the LPS- RPA-105.
  • Page 7: Using The Johnson Power Supply

    Using the Johnson Power Supply Network Communications 1. Verify that the InterOP8500 is addressed The InterOP8500 module supports several correctly. communications options through its CMnet port. 2. Turn the Johnson Controls panel power switch off. On a SuperVision system, the InterOP8500 3.
  • Page 8: Communicating With The Workstation

    InterOP8500 module using an APT and the On an ARC156 network segment (156 module’s Access Port (see Figure 11). This kbps), set the Comm Mode jumper to type of connection can be used to ARC156 (see Figure 8 for the switch’s...
  • Page 9: Input/Output

    Direct Network V-9010 200/61 V-9012 POS/ 200/61 Input/Output The InterOP8500 is equipped with 8 binary Power — — inputs, 15 analog inputs, and 16 binary Supply outputs. Any of the analog inputs can be used as digital inputs. Table 2 summarizes the...
  • Page 10: Unswitched And Switched Inputs

    B in a ry O u t p u ts B in a ry C o m m o n U n u s e d Figure 12. I/O Terminals for the Field Termination Board Revised 7/10/01 • InterOP8500 © 2001 Automated Logic Corporation...
  • Page 11 The InterOP8500 must be configured to receive the same type of input as the previously removed Johnson boards. Unsw itched Inputs 3. Set the InterOp8500 jumpers as follows: Jum p er in P la ce = Grip RTD M o d e •...
  • Page 12: Calculating Offset And Gain

    (2.5V - 0) and the user unit span is 100% for analog inputs to ensure the correct value (100% - 0%). Calculate the gain and offset for is read by the InterOP8500. You can also use a V-9012 feedback sensor like this: the custom translation table on the module driver Parameter page to read nonlinear 2.5 volts...
  • Page 13: Binary Inputs

    Binary Outputs Internal Power External Power (no isolation) (isolated) The InterOP8500 provides 16 binary outputs Figure 15. Binary I/O Power Jumper with a direct connection to the field termination board. The 16 binary outputs Binary Inputs have suppression. The binary output power The InterOP8500 provides 8 binary inputs requirement is 13.2VDC, which should be...
  • Page 14 LED10 LED22 LED23 * use point type of HOA Status Feedback and point number Figure 16. InterOp8500 HOA switches ** use channel numbers 81 - 80 To verify each output’s operation, lock the output to a known condition using the Function Block’s Properties page in WebCTRL...
  • Page 15: Point Identifiers

    Point Identifiers The following table shows the valid channel A point can be identified in WebCTRL by its numbers for each point on the InterOP8500. point number and point type; in SuperVision, The offset and gain values used depend on a point is identified by its channel number.
  • Page 16 Volts § § 0 to 5V -50° to 250° F 0.00 15.25‡ -46° to 121° C 0.00 UI 10 4 to 20mA mA or Volts § § 0 to 5V Revised 7/10/01 • InterOP8500 © 2001 Automated Logic Corporation...
  • Page 17: Transferring Memory

    FB). NOTE Since a failed download indicates a system problem, you should never clear The InterOP8500 module can store one a failure. Locate and resolve the problem, module driver and several FBs. The number then retry the download.
  • Page 18: Transferring Memory In Supervision

    Troubleshooting - Transfer Memory to detail to assist troubleshooting. Module. • In SuperVision v2.6b, download LED 1 Rx - lights when the InterOP8500 memory for This Module. receives data through the network segment. 4. When the memory transfer is finished, LED 2 Tx - lights when the InterOP8500 check the module status report again.
  • Page 19: Protection

    LED 24 Output Power - indicates power is Protection being received from field termination board The InterOP8500 module is protected by from the external power supply for binary internal solid state Polyswitches on the outputs and isolated binary inputs. incoming power and network connections.
  • Page 20: Sample Gfb

    Sample GFB Figure 17. Sample GFB Revised 7/10/01 • InterOP8500 © 2001 Automated Logic Corporation...