Emerson Copeland CORESENSE Technical Information page 17

Table of Contents

Advertisement

6.3.4 Status table
The current status of the CoreSense module can be read by using either register 0x117 (analog signal) or
0x97:0x9A (digital alarm). Please use only one of the 2 registers to read the current status of the module.
Status Table is used to decode the "module status" in Modbus address register 0x97:0x9A shown in Table 11 in
Chapter 6.3.2. The code sent by the module for status is a number that can be indexed into the table to decode the
state of the module.
Register 0097:009A is showing less than 64 bits in the table below, because only the alarm IDs that belong to
Stream CoreSense are shown. This register supports not only Stream CoreSense but also other Emerson
CoreSense products (for example CoreSense in Scroll).
Bit
Register 1
number
Normal running and fault
BIT0
temperature probe
Communication lost between
BIT1
current sensor and sensor
module
BIT2
Oil pressure warning
No communication to sensor
BIT3
module
Hardware configuration
BIT4
mismatch
BIT5
No communication to E2
BIT6
High discharge temp trip
BIT7
Compressor low voltage trip
BIT8
System trip
BIT9
Short cycle warning
BIT10
Open circuit warning
BIT11
Reserve phase lockout
BIT12
Welded contactor warning
BIT13
Module low voltage trip
BIT14
DLT fault warning
BIT15
Current sensor fault warning
Table 12: BIT alarm status table
Alarm
Module Status
ID
Normal running & fault discharge
7
temperature probe
Connection lost between current sensor and
12
sensor module
13
Insufficient oil pressure warning
16
No communication to sensor module
Hardware configuration mismatch (module
programmed to have a sensor module and it
17
is not detected or module programmed not to
have a sensor module and it is detected.)
18
No communication to rack controller
19
High discharge temperature trip
21
Compressor low voltage trip
Table 13: Status table
D7.8.6/1112-0815/E
Register 2
Voltage imbalance trip
Missing phase trip
Locked rotor trip
Motor overhead trip
Low oil pressure lockout
High discharge pressure
lockout
Locked rotor lockout
Missing phase lockout
Alarm
Module Status
ID
24
Voltage imbalance trip
28
Missing phase trip
31
Locked rotor trip
32
Motor overheat trip
37
Insufficient oil pressure lockout
39
High discharge temperature lockout
41
Locked rotor lockout
42
Missing phase lockout
CoreSense diagnostics control module failure
43
lockout
44
Normal Off
45
Normal running
46
Anti short cycle delay - time remaining
54
Low voltage lockout
Register 3
Control module failure
lockout
Normal Off
Normal running
Anti-short cycle time
delay
Compressor low voltage
trip lockout
Register 4
17/18

Advertisement

Table of Contents
loading

Table of Contents