Series-3000 VU52, VU53, VU54; VU442,
VU443, VU444; VU842, VU843, VU844 Fan
Coil Valves and Actuators
VU Fan Coil Actuator and Valves

APPLICATION

The VU442/VU842, VU443/VU843, and VU444/VU844
Fan Coil Valve Actuators are used in conjunction with the
VU52, VU53 and VU54 valves for 2-position control of low
pressure steam, or hot and chilled water with up to 50%
glycol in commercial HVAC equipment such as fan coil
units, terminal reheat coils and convectors. These valves
are humidity resistant and are suitable for use in
condensing, noncorrosive environments.
IMPORTANT
These valves are not for use in open systems or for
control of potable water.
Contents
Application .....................................................................................
Features ..........................................................................................
Specifications ...............................................................................
Installation .....................................................................................
Wiring ...............................................................................................
Operation .......................................................................................
Checkout .........................................................................................
Service .............................................................................................

FEATURES

• Compact construction for easy installation.
• Fits under the cover of most baseboard convectors
with actuator fitted.
ACTUATOR
• One-button, quick actuator release.
• Secure 3-point, metal latch to valve body.
• Spring return operation.
• Stainless steel case and aluminum cover.
• Line or low voltage, rust-resistant motors.
• Slotted conduit hole for faster wiring.
• Connecting leads available up to 8 feet (2.4 m) long.
• Manual opener for valve operation with automatic
return when power is restored.
• Actuator may be reinstalled or serviced without
draining the system or disassembling the valve.
• VU442, VU842 actuators fit 2-way VU52 valve bodies.
• VU443, VU843 actuators fit 2-way VU53 valve bodies.
• VU444, VU844 actuators fit 3-way VU54 valve bodies.
VALVE
• VU52, VU53 provide 2-way, straight-through control
of water, or low pressure steam with Class F motors.
• VU54 provides 3-way mixing or diverting control of
water.
• 300 psi (2,000 kPa, PN20) operating pressure rating.
• 15 psi low pressure steam rating for 2-way products
• Patented ball plug provides long service life, soft
close off.
• Triple stem O-ring seal.
• Quick opening flow curve for rapid response.
1
• Choice of sweat, f-NPT, or inverted flare connections.
1
2
5
7
7
8
8
PRODUCT DATA
95C-10885-01

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 3000 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Honeywell Home 3000 Series

  • Page 1 Series-3000 VU52, VU53, VU54; VU442, VU443, VU444; VU842, VU843, VU844 Fan Coil Valves and Actuators PRODUCT DATA FEATURES • Compact construction for easy installation. • Fits under the cover of most baseboard convectors with actuator fitted. ACTUATOR • One-button, quick actuator release. •...
  • Page 2 SERIES-3000 VU52, VU53, VU54; VU442, VU443, VU444; VU842, VU843, VU844 FAN COIL VALVES AND ACTUATORS SPECIFICATIONS Table 1. Series-3000 VU fan-coil valve actuator models Electrical Ratings Timing, sec. Temperature Auxiliary Model Type With Voltage Current Power Connections Open Close Rating Switch Comments VU442...
  • Page 3 SERIES-3000 VU52, VU53, VU54; VU442, VU443, VU444; VU842, VU843, VU844 FAN COIL VALVES AND ACTUATORS Max. Fluid Temperature: Max. Operating Pressure Rating: 249°F (120 C) Water: 300 psig (2000 kPa), PN20. Steam: 15 psig (No superheat allowed; 2-way bodies only) Min.
  • Page 4 SERIES-3000 VU52, VU53, VU54; VU442, VU443, VU444; VU842, VU843, VU844 FAN COIL VALVES AND ACTUATORS 1-3/4 1-3/4 1-3/4 1-3/4 7/8 DIA. 2-3/8 (44) (44) (44) (44) (22) (60) 3-3/4 (133) 1-1/2 (10) (38) (10) VU ACTUATOR 7/8 (23) 2-WAY 3-WAY 15/32 (12) VU53 VALVE WITH ACTUATOR VU52, VU53 AND VU54 VALVE DIMENSIONS WITH ACTUATOR...
  • Page 5 SERIES-3000 VU52, VU53, VU54; VU442, VU443, VU444; VU842, VU843, VU844 FAN COIL VALVES AND ACTUATORS (1) Locate the flow rate at the bottom of the graph. (2) Draw a line up from the flow rate to the inter- section of the curve. (3) Draw a line from the intersection to the left edge of the graph to determine the pressure drop in psi, or to the right edge to determine...
  • Page 6 SERIES-3000 VU52, VU53, VU54; VU442, VU443, VU444; VU842, VU843, VU844 FAN COIL VALVES AND ACTUATORS To Install & Remove Actuator INSTALLING ACTUATOR ON VU-SERIES VALVE BODY ASSEMBLY (See Fig. 5): 1. Orient flats on stem of VU-series valve body at 90° to water flow (toward notch in side of body).
  • Page 7 SERIES-3000 VU52, VU53, VU54; VU442, VU443, VU444; VU842, VU843, VU844 FAN COIL VALVES AND ACTUATORS REMOVING ACTUATOR FROM THE 4. Connect cable and actuator wires. 5. Slide cable wires down through slot in the wiring VU-SERIES VALVE BODY ASSEMBLY hole, so that the strain relief nut is inside the actua- (See Fig.
  • Page 8 95C-10885—01 M.S. Rev. 08-21 | Printed in United States © 2021 Resideo Technologies, Inc. All rights reserved. The Honeywell Home trademark is used under license from Honeywell International, Inc. This product is manufactured by Resideo Technologies, Inc. and its affiliates.

This manual is also suitable for:

Vu52Vu53Vu54Vu442Vu443Vu444 ... Show all

Table of Contents