AD1500 iQ

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AD1500 iQ and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Bofa AD1500 iQ

  • Page 1 AD1500 iQ...
  • Page 2: Table Of Contents

    Contents Overview 1 01 Overview of your iQ extraction system (front) Overview of your iQ extraction system (back) Overview of LCD display Safety Instructions Important safety notes Safety labels Before Installation 3 01 Unpacking and unit placement Installation 4 01 Fume capture methods Connecting to power supply Optional added features...
  • Page 3 Overview USB Port Control Panel Combined Filter Company Key Lock Door Branding Catch LCD Display Combined Filter Lever Filter Stops Door Catches Lever Location Lockable Castors Bracket Pre Filter...
  • Page 4 Overview Main Isolation Switch Motor Cooling Over-current Trips Signal Cable Inlet Mains Inlet Exhaust Outlet Air Inlet...
  • Page 5 Overview...
  • Page 6 This does not signify a dangerous or harmful resolved, please: situation. Refer to manual when this symbol is displayed.  Visit our website at www.bofa.co.uk for on-line help.  Electrical Safety Or contact the helpline on +44 (0) 1202 699444, The AD 1500 iQ system has been designed to meet the Mon-Fri, 9am-5pm.
  • Page 7 Safety Instructions Serial Number Label Warning and Information labels The following listing details labels used on your AD1500 iQ Location: Top right on the right hand side panel. unit. Meaning: This label contains a variety of information about the extraction unit, including.
  • Page 8 Ensure that 500 mm space is available around any vented Before installation panels on the extractor to ensure adequate airflow. 3. With the unit in position lock the 2 front castors. Inner transit packaging removal & unit placement Before installation, check the extraction unit for damage. All packaging must be removed before the unit is connected to the power supply.
  • Page 9 Installation Enclosures The AD1500 iQ has been designed to remove and filter fume The extraction hose and nozzle can be attached to the containing potentially hazardous particulate and gases enclosure surrounding the marking zone provided that the generated during manufacturing processes. Such hazardous extraction point is within 50-75mm of the marking point.
  • Page 10: Connecting To Power Supply

    The supply cord should only be replaced by a BOFA engineer as an electrical safety test may be required after replacement. The iQ system MUST be connected to a properly earthed outlet.
  • Page 11: Optional Added Features

    The extractor will need to be turned on and be out of Installation standby mode (See section for turning the extractor on) in order for this feature to operate. Volt free input This configuration requires the Black & Red cores of the signal cable (see section for location) to be connected together, in order to start the extractor.
  • Page 12 Separated Signal Installation With this configuration the Filter blocked & System fail signals will be separated to give 2 individual signals. When the filters become blocked the connection between the Green & White cables will become “Open” If the iQ system develops a fault (Refer to section Troubleshooting &...
  • Page 13 Changing the display units Operation The Airflow and temperature readings can be displayed in 2 ways. Temperature displayed as Airflow displayed as m 2. Temperature displayed as Airflow displayed as CFM Turning extraction unit On There are 2 stages to powering up your iQ extraction unit. The display value can be changed by pressing the “Enter”...
  • Page 14: Setting The Airflow

    Operation Setting the desired airflow The iQ system features automatic flow control. This enables the user to set the required airflow rate, then over time as the filters begin to block the motor will automatically begin to increase in speed to compensate for any loss in performance caused by the added restriction of the partially blocked filters.
  • Page 15: Airflow Auto Adjust (First Installation Only)

    Operation Airflow Auto Adjust (first installation only) When first setting the airflow on your new extraction unit the iQ will detect if the desired airflow is achievable with the installation that has been connected to the extraction unit. If the installation is causing too much restriction for the desired airflow to be reached, the Auto Adjust feature will be activated.
  • Page 16 when the filter icon is filled that particular filter will need Maintenance replacing. Pre Filter blocking Combined Filter Blocking Maintenance UK It is a legal requirement, under regulation 9 of the COSHH regulations that all local exhaust ventilation systems are thoroughly examined and tested at least once every 14 months (typically carried out annually).
  • Page 17: 01 Cleaning The Unit / Pre Filter Replacement

    To remove and replace the Combined filter follow the Maintenance procedure detailed below. Isolate the electrical supply to the extractor 2. Undo the catches on the front of the unit and open the door. The Combined filter is the higher of the 2 filters (refer to section for filter location) rotate the lever Pre Filter Replacement...
  • Page 18: Visual Alarms (Cont'd)

    iQ System Display Hose blocked alarm The iQ system features a 2 stage Hose blocked alarm.  Partial hose blockage  Full hose blockage Partial hose blocked alarm This alarm will become active when the iQ system detects a iQ Display Features part blockage in the installation.
  • Page 19 If the VOC level in the exhaust exceeds the PPM (Parts per million) level pre-set at BOFA then the Gas alarm will be triggered and display the Gas icon as shown below.
  • Page 20: Usb Connectivity / Usb Upload

    iQ System Display USB Connectivity The iQ system is equipped with a USB drive, that operates as a 2 way device, as detailed below.  Duplicating iQ settings  Download iQ Data Duplicating iQ settings (USB Upload) This USB upload feature has been designed for customers that have multiple extractors and specific set of parameters that they wish to duplicate across their iQ extraction units.
  • Page 21 iQ System Display Download iQ Data (USB Download) With this feature the customer is able to download all stored data within the iQ system, this information can then be used to keep records of how your iQ system is performing, this is also very beneficial for the technical team when diagnosing issues with the extraction system.
  • Page 22 5% increments, but with this downloadable file the pre is detected, for analysis of any faults in this column please filter blockage is shown as an exact percentage of its full contact the BOFA helpline. capacity. Combined filter % blockage...
  • Page 23 In the event of an error code being displayed please contact Independent Motor Failure Detection your local representative or BOFA who will be able to If the extraction unit develops a fault relating to one of the diagnose the fault and advise on the most efficient solution.
  • Page 24: 01 Consumable Spares / Filter Disposal

    The To maintain performance it is important that the filters are thresholds for these risks replaced with identical BOFA filters. To re-order please refer can then be compared with to the Filter number printed on the filter installed in your the amount of material in extraction unit.
  • Page 25 System Specifications Unit: AD 1500 IQ Capacity: 1250m /h (734cfm) Weight: 160Kg (353lbs) Motor: Centrifugal Fan Output: 3300w Electrical supply: 230v Hertz: 50/60Hz Full Load Current: 24.0A Noise Level: Below 68dB (A) (at typical operating speed) Size: Metric Imperial (mm) (inches) Height 1201...
  • Page 26 Contact Information BOFA Headquarters 21-22 Balena Close Creekmoor industrial Estate Poole Dorset BH17 7DX Phone: +44 (0) 1202 699444 BOFA Americas 303 S.Madison Street Staunton Illnois 62088 Phone: 001 (618) 205-5007...