Power Management
PML630/Compact Load-Shedding Solution
Product version: 1.2.1
Functions inherited from 630 series
Table 22. Multipurpose analog protection (MAPGAPC)
Characteristic
Operate time accuracy
Table 23. Multipurpose analog protection (MAPGAPC) main settings
Parameter
Operation mode
Start value
Start value Add
Operate delay time
Table 24. Station battery supervision (SPVNZBAT)
Characteristic
Operation accuracy
Operate time accuracy
Table 25. Three-phase current measurement (CMMXU)
Characteristic
Operation accuracy
Suppression of harmonics
30
Function
MAPGAPC
MAPGAPC
MAPGAPC
MAPGAPC
Value
±1.0% of the set value or ±20 ms
Value (Range)
Over
Under
-10000.0...10000.0
-100.0...100.0
0.00...200.00 s
Value
±1.0% of the set value
±1.0% of the set value or ±40 ms
Value
At the frequency f = f
n
±0.5% or ±0.002 × I
n
(at currents in the range of 0.01...4.00 × I
DFT: -50 dB at f = n × f
, where n = 2, 3, 4, 5,...
n
RMS: No suppression
1MRS757334 E
Step
-
0.1
0.1
0.01
)
n
ABB