Technical specifications
Article number
OPC UA
60
Runtime license required
OPC UA Client
Application authentication
Security policies
User authentication
Number of connections, max.
Number of nodes of the client interfaces,
max.
Number of elements for one call of
OPC_UA_NodeGetHandleList/OPC_UA_Rea
dList/OPC_UA_WriteList, max.
Number of elements for one call of
OPC_UA_NameSpaceGetIndexList, max.
Number of elements for one call of
OPC_UA_MethodGetHandleList, max.
Number of simultaneous calls of the client
instructions per connection (except
OPC_UA_ReadList,OPC_UA_WriteList,OPC_
UA_MethodCall), max.
Number of simultaneous calls of the client
instructions
OPC_UA_ReadList,OPC_UA_WriteList and
OPC_UA_MethodCall, max.
Number of registerable nodes, max.
Number of registerable method calls of
OPC_UA_MethodCall, max.
Number of inputs/outputs when calling
OPC_UA_MethodCall, max.
OPC UA Server
Application authentication
Security policies
User authentication
GDS support (certificate management)
Number of sessions, max.
Number of accessible variables, max.
Number of registerable nodes, max.
Number of subscriptions per session, max.
Sampling interval, min.
Publishing interval, min.
6ES7518-4AX00-1AB0
Yes; "Large" license required
Yes
Yes
Available security policies: None, Basic128Rsa15,
Basic256Rsa15, Basic256Sha256
"anonymous" or by user name & password
40
5 000
300
20
100
1
5
5 000
100
20
Yes; Data access (read, write, subscribe), method
call, custom address space
Yes
Available security policies: None, Basic128Rsa15,
Basic256Rsa15, Basic256Sha256
"anonymous" or by user name & password
Yes
64
200 000
50 000
20
10 ms
10 ms
CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AB0)