Siemens SIMATIC S7-1500 Manual page 59

Cpu 1518-4 pn/dp mfp
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Technical specifications
Article number
PROFIBUS DP master
Services
Interface types
RJ 45 (Ethernet)
RS 485
Protocols
Number of connections
Redundancy mode
Media redundancy
58
Number of connections, max.
Number of DP slaves, max.
PG/OP communication
Equidistance
Isochronous mode
Activation/deactivation of DP slaves
100 Mbps
1000 Mbps
Autonegotiation
Autocrossing
Industrial Ethernet status LED
Transmission rate, max.
Number of connections, max.
Number of connections reserved for
ES/HMI/web
Number of connections via integrated inter-
faces
Number of S7 routing paths
H-Sync forwarding
Media redundancy
MRP
MRP interconnection, supported
MRPD
Switchover time on line break, typ.
Number of stations in the ring, max.
6ES7518-4AX00-1AB0
48; for the integrated PROFIBUS DP interface
125; In total, up to 1 000 distributed I/O devices
can be connected via AS-i, PROFIBUS or PROFINET
Yes
Yes
Yes
Yes
Yes
Yes; Only possible at the X3 interface of the CPU
1518
Yes
Yes
Yes
12 Mbit/s
384; via integrated interfaces of the CPU and
connected CPs / CMs
10
320
64; in total, only 16 S7-Routing connections are
supported via PROFIBUS
Yes
only via 1st interface (X1)
Yes; MRP Automanager according to IEC 62439-2
Edition 2.0, MRP Manager; MRP Client
Yes; as MRP ring node according to IEC 62439-2
Edition 3.0
Yes; Requirement: IRT
200 ms; For MRP, bumpless for MRPD
50
CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AB0)
Equipment Manual, 07/2021, A5E40882737-AB

Advertisement

Table of Contents
loading