Drive's Power Connection Terminals (Supplement to Aquavar CPC User's Manual)
The following tables show maximum wire size and required tightening torque for incomming
power and motor terminals, and grounding terminal lug information.
208...240 Volt, Terminals
208 ... 240 Volt
HP
Type Code
1
CPC2004xFD
2
CPC2007xFD
3
CPC2012xFD
5
CPC2017xFD
7.5
CPC2024xFD
10
CPC2031xFD
15
CPC2046xFD
20
CPC2059xFD
25
CPC2075xFD
30
CPC2088xFD
40
CPC2114xFD
50
CPC2143xFD
60
CPC2178xFD
75
CPC2221xFD
100
CPC2248xFD
NOTE: "x" represents both NEMA 1 and NEMA 12.
Frame
Circuit
Size
Breaker
R1
R1
62 in-lbs
R1
R1
R2
#6
62 in-lbs
R2
R3
#3
R3
62 in-lbs
#1/0
R4
62 in-lbs
R4
#2/0
200 in-lbs
R4
200 in-lbs
R6
300 MCM 300 MCM
R6
200 in-lbs 200 in-lbs
2 x 250
R6
MCM
R6
275 in-lbs 275 in-lbs
Power Wiring Data
Dis-
Motor
connect
Terminals
Switch
7 in-lbs
12 in-lbs
#8
7 in-lbs
#8
#6
12 in-lbs
18 in-lbs
#3
#3
18 in-lbs
24 in-lbs
#1/0
55 in-lbs
#1/0
#1/0
70 in-lbs
180 in-lbs
#2/0
300 MCM
354 in-lbs
2 x 250
350 MCM
MCM
354 in-lbs
Ground
Lugs
NEMA
1 & 12
#4
35 in-lbs
#2
50 in-lbs
3 x #3/0
250 in-lbs