TECHNICAL DATA
500...600 Volt Fuses
500 ... 600 Volt
HP
Identification
2
CPC5002xFD
3
CPC5004xFD
5
CPC5006xFD
7.5
CPC5009xFD
10
CPC5011xFD
15
CPC5017xFD
20
CPC5022xFD
25
CPC5027xFD
30
CPC5032xFD
40
CPC5041xFD
50
CPC5052xFD
60
CPC5062xFD
75
CPC5077xFD
100
CPC5099xFD
125
CPC5125xFD
150
CPC5144xFD
NOTE: "x" represents both NEMA 1 and NEMA 12 enclosures.
Input Power Cables / Wiring – R7/R8
Based on:
• NEC Table 310-16 for copper wires
• 90 °C (194 °F) wire insulation
• 40 °C (104 °F) ambient temperature
• Not more than three current-carrying conductors in raceway or cable, or earth (directly buried).
• Copper cables with concentric copper shield
Max Load Current (A)
345
391
410
465
22
Base
Drive
Frame
Size
R2
R2
R2
R2
R2
R2
R3
R3
R4
R4
R4
R4
R6
R6
R6
R6
Cu Wire Size (AWG/kcmil)
400 MCM or 2 x 2/0
500 MCM or 2 x 3/0
2 x 3/0
2 x 4/0
Drive Input Fuse Ratings
Amps
Bussmann
(600V)
15
15
15
15
30
30
50
50
100
100
100
100
125
170M1368
125
170M1368
160
170M1369
200
170M1370
NEC
Max Load Current (A)
474
534
615
711
Type
KTK-R-15
KTK-R-15
KTK-R-15
KTK-R-15
KTK-R-30
KTK-R-30
JJS-50
JJS-50
JJS-100
JJS-100
JJS-100
JJS-100
Cu Wire Size (AWG/kcmil)
2 x 250
2 x 300
2 x 350
2 x 500