Safety Instructions Precautions to be taken with a Congratulations for choosing a product from CG Drives & Automation! connected motor Before you begin with installation, commissioning or If work must be carried out on a connected motor or on the...
Page 4
IT Mains supply The AC drives can be modified for an IT mains supply, (non-earthed neutral), please contact your supplier for details. Alarms Never disregard an alarm. Always check and remedy the cause of an alarm. CG Drives & Automation 01-7694-01r0...
Technical Data ..........33 Drive data ..............33 Power losses and flow ..........36 General electrical specifications......38 Dimensions and Weights........39 Derating ..............41 Environmental conditions........41 Water cooling............42 DC fuses for VSI units ..........44 CG Drives & Automation, 01-7694-01r0...
By using the optional “Extended EMC” filter the AC drive fulfils requirements according to category C2. WARNING! In a domestic environment this product may cause radio interference, in which case it may be necessary to take adequate additional measures. Introduction CG Drives & Automation 01-7694-01r0...
Page 9
UL 840 Insulation coordination including clearances and creepage distances for electrical equipment. CNL (Canadian National Standards - Listed) complying with the requirements of CAN/CSA C22.2 No. 14-10 Industrial Control Equipment. Russian For all sizes. CG Drives & Automation 01-7694-01r0 Introduction...
CAUTION! equipment. By ensuring this product is disposed of correctly, Always consult CG Drives & Automation before connecting an Emotron AFR/AFG to a you will help prevent potentially negative consequences for standard VSI.
). Other features are the possibility for reactive power compensation and boosted DC-link voltage. AFR/AFG AFR/AFG = AFE + LCL-filter FDUL/VFXR = AFR + VSI (FDU/VFX) FDUG/VFXG = AFG + VSI (FDU/VFX) Fig. 2 VSI with AFR/AFG. CG Drives & Automation 01-7694-01r0 Introduction...
Page 12
THD(I) below 5%. AFR offers standard AFE functionality such as: Active power control. Reactive power control. Low harmonic operation. AFR= AFE + LCL filter Fig. 3 Introduction CG Drives & Automation 01-7694-01r0...
* For larger units, Q1 Main switch and K1 Main contact are replaced by Q1 Motorized circuit breaker. NOTE: For AFG/FDUG/VFXG, supply voltage measurement board (SVMB) is mandatory. It is mounted and connected internally to K2. CG Drives & Automation 01-7694-01r0 Introduction...
* For larger units, Q1 Main switch and K1 Main contact are replaced by Q1 Motorized circuit breaker. NOTE: For AFG/FDUG/VFXG, supply voltage measurement board (SVMB) is mandatory. It is mounted and connected internally to K2. Introduction CG Drives & Automation 01-7694-01r0...
Permitted load (F) 45 ° 4 800 N (1080 lbf) 60 ° 6 400 N (1439 lbf) 90 ° 13 600N (3057 lbf) Note: Calculated load F as F [N] = m [kg] x 9.81. CG Drives & Automation 01-7694-01r0 Mounting...
Page 16
F1 = 7000 N F1 = 7000 N F2 = 7000 N F2 = 14000 N F3 = 7000 N Fig. 7 Enclosure combination with internal brackets. Fig. 8 Enclosure combination with internal brackets. Mounting CG Drives & Automation 01-7694-01r0...
Page 17
For the enclosure combination with internal baying brackets the following load capacities are supported: Max. 7000 N Max. 15000 N Max. 14000 N Max. 15000 N Max. 7000 N Fig. 10 Transport of enclosure combination with fork-lift truck. CG Drives & Automation 01-7694-01r0 Mounting...
Control Connection Control board location Fig. 11 Control board location (example FDUL46-1710-CL (left side AFR, right side VSI) CG Drives & Automation 01-7694-01r0 Control Connection...
SELV voltage signals to the relay AnOut 1 Min speed to max speed terminals of this option board while AnOut 2 0 to max torque connecting all 230VAC signals to the control board relay terminals 31 - 52. CG Drives & Automation 01-7694-01r0 Control Connection...
AnIn4 Current (default) NOTE: Scaling and offset of AnIn1 - AnIn4 can be configured using the software. NOTE: the 2 analogue outputs AnOut 1 and AnOut 2 can be configured using the software. Control Connection CG Drives & Automation 01-7694-01r0...
Page 23
It is important not to enable any additional termination apart from the two in each cable end as it will impose as an additional load for a transmitting transceiver and may cause malfunctioning. CG Drives & Automation 01-7694-01r0 Control Connection...
1 kΩ / ¼ W type potentiometer for best control linearity. *** Optional terminals X1: 78 - 79 for connection of Motor-PTC on frame sizes B, C and D. Fig. 13 Connection example. Control Connection CG Drives & Automation 01-7694-01r0...
Also refer to schematic set included with drive delivery. NOTE: See tightening torque in chapter 4.3.1. Motor connection Main supply Ground / earth connection connection bus bar Fig. 14 Typical cables connection in cabinet. CG Drives & Automation 01-7694-01r0 Installation...
Mains voltage used. Symmetrical three conductor cable with concentric protection (PE) wire or a four Motor conductor cable with compact low-impedance concentric shield for the voltage used. Control cable with low-impedance shield, Control screened. Installation CG Drives & Automation 01-7694-01r0...
Page 27
FDUL/VFXR46-2500-CL 2 x 1250 8 x bolt M12** 10/40 Nm 8 x bolt M12 10/40 Nm 8 x bolt M12 40 Nm * Tunnel clamp ** Bolt clamp *** For symmetrical EMC cable (3xPE) CG Drives & Automation 01-7694-01r0 Installation...
Page 28
2 x 1000 2 x 8xBolt M12 10/40 Nm 4 x 4x bolt M12 10/40 Nm 12 x bolt M12 40 Nm * Tunnel clamp ** Bolt clamp *** For symmetrical EMC cable (3xPE) Installation CG Drives & Automation 01-7694-01r0...
Page 29
2 x 1600 8 x bolt M12** 10/40 Nm 6 x bolt M12 40 Nm AFR69-3600-CL 4 x 1000 2x5 bolt M12** 10/40 Nm 6 x bolt M12 40 Nm * Tunnel clamp ** Bolt clamp CG Drives & Automation 01-7694-01r0 Installation...
The liquid temperature is indirectly controlled with an internal temperature circuit of the AC drive. This will switch off the AC drive if the internal temperature becomes too high. Fig. 17 Typical cooling section. CG Drives & Automation 01-7694-01r0 Water cooling...
This will switch off the AC drive if the internal temperature becomes too high. Fig. 19 shows water connections without a cooling section. Water pipe connections (In/Out) are of type G1. Fig. 19 Water connections. Water cooling CG Drives & Automation 01-7694-01r0...
6.1.1 Technically qualified personnel Installation, commissioning, demounting, making measurements, etc., of or at the motor inverter may only be carried out by personnel technically qualified for the task. CG Drives & Automation 01-769401r0 Troubleshooting...
Maintenance The first year inspection includes the following tasks: • Disconnect the quick couplers and check for visible resi- due. Please report abnormalities to CG Drives & Auto- 6.2.1 Check of the liquid mation. In time the liquid can get contaminated by floating particles •...
FDUL/VFXR46-2200-CL 2640 2200 1250 1760 1000 FDUL/VFXR46-2500-CL 3000 2500 1350 2000 1120 * Available during limited time and as long as allowed by drive temperature. ** PEBB= Power Electronic Building Block (power module). CG Drives & Automation 01-7694-01r0 Technical Data...
Page 36
1120 AFR46-1770-CL 2124 1770 1200 1416 AFR46-2100-CL 2520 2100 1425 1680 1140 * Available during limited time and as long as allowed by drive temperature. ** PEBB= Power Electronic Building Block (power module). Technical Data CG Drives & Automation 01-7694-01r0...
Page 37
AFR69-2700-CL 3240 2700 3150 2160 2520 AFR69-3600-CL 4320 3600 4200 2880 3360 * Available during limited time and as long as allowed by drive temperature. ** PEBB= Power Electronic Building Block (power module). CG Drives & Automation 01-7694-01r0 Technical Data...
FDUL/VFXR46-1710-CL FDUL/VFXR46-2200-CL FDUL/VFXR46-2500-CL 7.2.2 FDUL/VFXR 690 V units Table 25 Losses in water Losses in air Water flow Model (kW) (kW) (l/min) FDUL/VFXR69-200-CL FDUL/VFXR69-250-CL FDUL/VFXR69-500-CL FDUL/VFXR69-750CL FDUL/VFXR69-1000-CL FDUL/VFXR69-1250-CL FDUL/VFXR69-1500-CL FDUL/VFXR69-2000-CL FDUL/VFXR69-3000-CL FDUL/VFXR69-4000-CL 2x70 Technical Data CG Drives & Automation 01-7694-01r0...
Page 39
AFR46-1050-CL AFR46-1400-CL 12,5 AFR46-1770-CL AFR46-2100-CL 7.2.4 AFR 690 V Table 27 Losses in water Losses in air Water flow Model (kW) (kW) (l/min) AFR69-175-CL AFR69-233-CL AFR69-466-CL AFR69-700-CL AFR69-900-CL AFR69-1400-CL AFR69-1800-CL AFR69-2100-CL AFR69-2700-CL AFR69-3600-CL CG Drives & Automation 01-7694-01r0 Technical Data...
-10VDC - 10 V @10 mA +24VDC +24 V Short-circuit current +100 mA max (together with Digital Outputs) Standby supply Standby supply input voltage for control unit. 24 VDC ±10% (max 1A consumption) Technical Data CG Drives & Automation 01-7694-01r0...
Page 42
5600 2774 / +350 (6116 /+772) NOTE: A connection cabinet is needed if for example a battery system is connected to the DC busbars at the top of the cabinet. Contact the supplier. Technical Data CG Drives & Automation 01-7694-01r0...
WARNING! If the device is stored for more than two years, the DC link capacitor of the devices must be reformed during commissioning. The reforming procedure is described in manual “Capacitor reforming unit”. CG Drives & Automation 01-7694-01r0 Technical Data...
Page 45
(open / closed), advice is to check supplier of glycol for the exact values. Typical use water/antifreeze mixture of 70 % water and 30 % glycol. CG Drives & Automation 01-7694-01r0 Technical Data...
Need help?