Samsung AJ BNHDCH Series Installation Manual page 33

Table of Contents

Advertisement

Option
SEG13
Explanation
PAGE
Indication
Details
Indication and
Details
2
Option
SEG17
Explanation
Buzzer control
Indication
Details
0
Use of buzzer
Indication and
Details
1
Disuse
Option
SEG21
Explanation
Heating setting compensation
Indication
Details
0
Disuse
Indication and
1
3.6°F (2°C)
Details
2
9°F (5°C)
• 1) SEG4
By SEG4 setting, Minimizing fan operation when thermostat is off.
- Fan operates for 20 seconds at an interval of 5 minutes in heat mode.
- Fan stops or operates Ultra low in Cooling when thermostat is off.
• 2) SEG18
If you set the Maximum filter usage time option to a value other than 2 and 6, it is automatically set to 2 (1000 hours).
• 3) SEG20
If you set the Individual control with remote control option to a value other than 0 to 4, it is automatically set to 0 (Indoor 1)
• 4) SEG21
SEG14
Use of external control
Indication
Details
0
Disuse
Sub,
1
On/Off
Existing
2
Off
Control
3
Window
4
Disuse
Main,
5
On/Off
Existing
6
Off
Control
7
Window
8
Disuse
Sub,
9
On/Off
Reverse
A
Off
Control
B
Window
C
Disuse
Main,
D
On/Off
Reverse
E
Off
Control
F
Window
SEG18
2)
Maximum filter usage time
Indication
Details
2
1000 Hour
6
2000 Hour
SEG22
4)
RESERVED
SEG15
Setting the output of external control
Indication
Details
0
Thermo on
1
Operation on
SEG19
PAGE
Indication
Details
3
SEG23
Away Set OFF Timer
Indication
Details
0 or 1
Auto Set OFF 30Min.
2
Auto Set OFF 60Min.
3
Auto Set OFF 120Min.
4
Auto Set OFF 180Min.
SEG16
RESERVED
SEG20
3)
Individual control with remote control
Indication
Details
0 or 1
Indoor 1
2
Indoor 2
3
Indoor 3
4
Indoor 4
SEG24
RESERVED
English
33

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aj009bnhdchAj012bnhdchAj015bnhdchAj018bnhdch

Table of Contents