Goodman CVC97 Series Technical Manual page 9

97% gas furnace units
Table of Contents

Advertisement

BLOWER PERFORMANCE SPECIFICATIONS
*MVM971005CNA
(@ .1" - .8" w.c. ESP)
Tap
Adjust
Minus 10%
A
Normal
Plus 10%
Minus 10%
B
Normal
Plus 10%
Minus 10%
C
Normal
Plus 10%
Minus 10%
D
Normal
Plus 10%
*MVM971205DNA
(@ .1" - .8" w.c. ESP)
Tap
Adjust
Minus 10%
A
Normal
Plus 10%
Minus 10%
B
Normal
Plus 10%
Minus 10%
C
Normal
Plus 10%
Minus 10%
D
Normal
Plus 10%
Notes
All furnaces ship as high speed for cooling. Installer must adjust blower
speed as needed.
For most jobs, about 400 CFM per ton when cooling is desirable.
CFM between .5" and .8" w.c. is tabulated for cooling purposes only.
Cooling Speed
High-Stage
Low-Stage
CFM
CFM
738
508
820
564
902
620
1,020
706
1,133
784
1,246
862
1,318
884
1,464
982
1,610
1,080
1,562
1,133
1,736
1,259
1,910
1,385
Cooling Speed
High-Stage
Low-Stage
CFM
CFM
780
492
867
547
954
602
1,044
748
1,160
831
1,276
914
1,320
918
1,467
1,020
1,614
1,122
1,719
1,150
1,910
1,278
2,101
1,406
*MVM971005CNA
Heating Speed
(@ .1" - .5" w.c. ESP; Rise Range: 35 - 65°F)
High-Stage
Tap
Adjust
Minus 10%
A
Normal
Plus 10%
Minus 10%
C
Normal
Plus 10%
Minus 10%
D
Normal
Plus 10%
Minus 10%
D
Normal
Plus 10%
*MVM971205DNA
Heating Speed
(@ .1" - .5" w.c. ESP; Rise Range: 35 - 65°F)
High-Stage
Tap
Adjust
Minus 10%
A
Normal
Plus 10%
Minus 10%
C
Normal
Plus 10%
Minus 10%
D
Normal
Plus 10%
Minus 10%
D
Normal
Plus 10%
Rise
CFM
(°F)
1,636
55
1,818
49
2,000
45
1,683
53
1,870
48
2,057
44
1,719
52
1,910
47
2,101
43
1,761
51
1,957
46
2,153
42
Rise
CFM
(°F)
1,702
63
1,891
57
2,080
52
1,746
62
1,940
56
2,134
51
1,771
61
1,968
55
2,165
50
1,825
59
2,028
53
2,231
48
9