Mitsubishi Heavy Industries FDE40ZMXVG Technical Manual page 258

Inverter packaged air-conditioners
Table of Contents

Advertisement

Error code
Indoor control PCB
Remote control:
E41
Outdoor control PCB
Outdoor inverter
Note (1) 8-time flash FDC250 model only.
1. Applicable model
Model FDC200, 250VSA
2. Error detection method
When anomalously high
temperature is detected by
power transistor.
3. Condition of error displayed
Anomalously high temperature
of power transistor is detected 5
times within 60 minutes.
4. Presumable cause
• Inverter PCB anomaly
• Outdoor fan motor anomaly
• Improperly fixing of power
transistor to radiator fin
• Inadequate installation space
of outdoor unit
Note:
LED
Green
Keeps flashing
Keeps flashing
Yellow LED
PCB
2-time flash or 8-time flash
5. Troubleshooting
Is it possible to
reset the error for 10 minuted after
compressor stopped?
YES
Is the
installation space of outdoor
unit enough?
YES
Is the outdoor fan running?
YES
Is the fixing
of power transistor to radiator fin OK?
・ Fixed screw
・ Application of radiating
silicone
YES
Does the error recur?
Red
Content
Stays OFF
1-time flash
Power transistor overheat
(Models FDC200, 250VSA only)
(1)
Diagnosis
NO
NO
Replace inverter PCB
Can error be reset?
NO
Correct it.
NO
Replace the outdoor fan motor or the
outdoor control PCB.
YES
NO
244
-
-
'15 • PAC-T-236
  
Countermeasure
OK
YES
Replace power transistor.
NO
Fix properly.
NO
Defective inverter PCB ➞
Replace
OK

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents