(1) Auto operation
(a) If "Auto" mode is selected by the remote control, the heating and the cooling are automatically switched according to the
difference between outdoor air temperature and setting temperature and the difference between setting temperature and return
air temperature. (When the switching of cooling mode ↔ heating mode takes place within 3 minutes, the compressor does
not operate for 3 minutes by the control of 3-minute timer.) This will facilitate the cooling/heating switching operation in
intermediate seasons and the adaptation to unmanned operation at stores, etc (ATM corner of bank).
Heating operation
-3
Room temperature (detected with Th
Notes (1) Temperature range of switching cooling/heating mode can be changed by RC-EX1A from ±1.0 - ±4.0.
(2) Room temperature control during auto cooling/auto heating is performed
according to the room temperature setting temperature. (DIFF: ±1 deg)
(3) If the indoor heat exchanger temperature rises to 59°C or higher during
heating operation, it is switched automatically to cooling operation. In
addition, for 1 hour after this switching, the heating operation is not
performed, regardless of the temperature shown at right.
(b) The following automatic controls are performed other than (a) above.
  (i) Cooling or heating operation mode is judged according to the conditions of the "Judgment based on Setting temperature +
Cooling select temperature and Indoor return air temperature" and the "Judgment based on Outdoor temperature".
1)  I n "Setting temperature - Cooling select temperature < Indoor return air temperature" and "Outdoor temperature/Cooling <
Outdoor return air temperature" ⇒ Operation mode: Cooling
2)  " Setting temperature + Heating select temperature > Indoor return air temperature" and "Outdoor temperature/Heating >
Outdoor air temperature" ⇒ Operation mode: Heating
3) The outdoor air temperature of the above judgment conditions is sampled at every 10 minutes.
4) In the range where the above cooling and heating zones are overlapped ⇒ Forced thermostat OFF
Cooling operation
+3
Room temperature setting temperature
-A) [deg]
I
Cooling select temperature
30
28
26
Forced thermostat OFF
24
22
20
18
16
Heating
14
12
12
14
16
18
20
Indoor return air temperature (℃)
Heating OK
56
Indoor heat exchanger temperature (°C)
Heating select temperature
Cooling
Forced
thermostat OFF
Forced thermostat
OFF
22
24
26
28
30
Setting temperature
122
-
-
'15 • PAC-T-236
Heating operation stopped (cooling)
59
Outdoor temperature/Heating
Outdoor temperature/Cooling