Trane 4TTX8 Installer's Manual page 18

Table of Contents

Advertisement

STEP 2 - Determine the final subcooling value using total Line Length and Lift measured in STEP 1 and the charts below.
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
50
40
30
25
Use Design Subcooling
15
10
0
20
30
40
50
60
70
TOTAL REFRIGERANT LINE LENGTH (FT) - [ includes lift ]
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
50
40
30
25
Use Design Subcooling
15
10
0
20
30
40
50
60
70
TOTAL REFRIGERANT LINE LENGTH (FT) - [ includes lift ]
Design Subcooling Value = __________º F
(from nameplate or Service Facts)
Subcooling Correction = __________º F
Final Subcooling Value = __________º F
STEP 3 - Stabilize the system by operating for a
minimum of 20 minutes.
At startup, or whenever charge is removed or
added, the system must be operated for a mini-
mum of 20 minutes to stabilize before accurate
measurements can be made.
18
2 Ton AC
Add 2°
Add 1°
Add 1°
80
90 100 110 120 130 140 150
4 Ton AC
Add 4°
Add 2°
Add 1°
Add 1°
80
90 100 110 120 130 140 150
3 Ton AC
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
50
Add 1°
40
30
25
Use Design Subcooling
15
10
0
20
30
40
50
60
70
80
90 100 110 120 130 140 150
TOTAL REFRIGERANT LINE LENGTH (FT) - [ includes lift ]
5 Ton AC
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
50
40
30
25
Use Design Subcooling
15
10
0
20
30
40
50
60
70
80
90 100 110 120 130 140 150
TOTAL REFRIGERANT LINE LENGTH (FT) - [ includes lift ]
20 MIN.
Add 2°
Add 1°
Add 4°
Add 2°
Add 1°
Add 1°
18-AC95D1-5C-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

4ttx8024a4ttx8036a4ttx8048a4ttx8060a

Table of Contents