parameter is precisely fulfilled. If the setting of the "Operator panel available" parameter is not
fulfilled, the diagnostics message "Preset <> Actual Configuration" is output by the controller.
The following table shows the effects of the sample parameter values set:
Table 6-5
Set parameter values
"Operator panel availa‐
ble" = "yes" and
"Operation at Preset <>
Actual Configuration =
"Disable"
"Operator panel availa‐
ble" = "no" and
"Operation at Preset <>
Actual Configuration =
"Disable"
"Operator panel availa‐
ble" = "yes" and
"Operation at Preset <>
Actual Configuration =
"Enable"
"Operator panel availa‐
ble" = "no" and
"Operation at Preset <>
Actual Configuration =
"Enable"
The "Operation at Preset <> Actual Configuration" parameter can only be modified via IO‑Link. It
cannot be adjusted at the device.
Note
Parameter assignment for "Operation at Preset <> Actual Configuration" refers only to the
connectable operator panel.
By contrast, the diagnostics message "Preset <> Actual Configuration" can have different causes:
• The condition of the "Operator panel available" parameter is not fulfilled.
• Communication with current measuring module faulty.
• An incorrect current measuring module is connected.
SIRIUS 3RB24 electronic overload relay for IO-Link
Equipment Manual, 07/2022, NEB969165602000/RS-AA/003
Parameter setting - example of operation with operator panel
Practical implementation
Operator panel availa‐
ble
Operation of the solid-
state overload relay pos‐
sible.
The solid-state overload
relay trips. Further oper‐
ation of the device not
possible.
→ Fault message "Preset
<> Actual Configuration"
Operation of the solid-
state overload relay pos‐
sible.
Operation of the solid-
state overload relay pos‐
sible.
6.9 Operation with operator panel
Operator panel not
available
Operation of the solid-
state overload relay not
possible.
→ Fault message "Preset
<> Actual Configuration"
Operation of the solid-
state overload relay pos‐
sible.
Operation of the solid-
state overload relay pos‐
sible.
Operation of the solid-
state overload relay pos‐
sible.
Parameters
Operator panel is dis‐
connected during op‐
eration
The solid-state overload
relay trips. Further oper‐
ation of the device not
possible.
→ Fault message "Preset
<> Actual Configuration"
The group error (SF) is
reset automatically. Op‐
eration of the solid-state
overload relay possible.
Operation of the solid-
state overload relay pos‐
sible.
Operation of the solid-
state overload relay pos‐
sible.