United Electric Controls J21K Installation And Maintenance Instructions

Differential pressure switch

Advertisement

Quick Links

Please read all instructional literature carefully and thoroughly before starting. Refer to the final page for the listing of Recommended Practices, Liabilities
and Warranties.
GENERAL
BEFORE INSTALLING, CHECK THE SENSOR MODEL SELECTED
FOR COMPATIBILITY TO THE PROCESS MEDIA IN CONTACT
WITH THE SENSOR AND WETTED PARTS.
J21K Differential Pressure Switch utilizes opposing metal bellows to detect
pressure differences between two pressure sources. The bellows are
connected to a mechanical linkage. When the pressure at the high port
exceeds the pressure at the low port by a pre-determined amount, the
mechanism operates a snap-action electrical switch. The predetermined
actuation pressure can be adjusted by the user as described below.
Part I - Installation
MOUNTING
INSTALL UNIT WHERE SHOCK, VIBRATION AND TEMPERATURE
FLUCTUATIONS ARE
MOISTURE IS PREVENTED FROM ENTERING THE ENCLOSURE.
DO NOT MOUNT UNIT IN AMBIENT TEMPERATURES EXCEEDING
PUBLISHED LIMITS.
Surface mount in any position via two mounting ears. Never turn this unit
by grasping enclosure. Always hold a wrench on the bellows housing (or
fitting) when connecting pressure joints.
WIRING
DISCONNECT ALL SUPPLY CIRCUITS BEFORE WIRING UNIT.
WIRE UNITS ACCORDING TO NATIONAL AND LOCAL
ELECTRICAL CODES. MAXIMUM RECOMMENDED WIRE SIZE
IS 14 AWG.
ELECTRICAL RATINGS STATED IN LITERATURE AND ON
NAMEPLATES MUST NOT BE EXCEEDED, OVERLOAD ON A
SWITCH CAN CAUSE FAILURE ON THE FIRST CYCLE.
Differential Pressure Switch
Type J21K
Tools Needed
- Adjustable wrenches (2)
- Flat blade screwdriver
MINIMAL.
MOUNT UNIT SO THAT
UNITED ELECTRIC
CONTROLS
Installation and Maintenance
Instructions
Remove the two (2) screws retaining the cover and gasket. Remove cover.
Connect conduit to the enclosure using a conduit fitting that is suitable for
your installation. A watertight conduit fitting (option M900 or equivalent)
must be used for NEMA 4 protection. Wire directly to the switch terminals
in accordance with local and national electrical codes. Bring the wires up to
the terminals from the rear of the enclosure to prevent interference with the
mechanism.
Part II - Adjustments
For set point adjustment and re-calibration, connect the unit to a calibrated
pressure source.
Set point adjustment is achieved by varying the gap between the mechanical
actuator and the plunger on the electrical switch
J21K
To raise the differential pressure setting, turn the 5/16" hex head screw out
(to the left).
To lower the differential pressure setting, turn the 5/16" hex head screw in
(to the right).
IMJ21K-01
Tools Needed
- 5/16" open end wrench

Advertisement

loading

Summary of Contents for United Electric Controls J21K

  • Page 1 Bring the wires up to the terminals from the rear of the enclosure to prevent interference with the J21K Differential Pressure Switch utilizes opposing metal bellows to detect mechanism. pressure differences between two pressure sources. The bellows are connected to a mechanical linkage.
  • Page 2 Dimensions RECOMMENDED PRACTICES AND WARNINGS United Electric Controls Company recommends careful consideration of the following factors when specifying and installing UE pressure and temperature units. Before installing a unit, the Installation and Maintenance instructions provided with unit must be read and understood.