IDNet Device Types (continued)
MCOI
MCOIS
MCOH
MCOHS
MCOPH
MCOPHS
ANAMON
STANDARD BASE Standard TrueAlarm base (no head inserted)
SOUNDER BASE
RELAY BASE
ISOLATOR BASE
CO BASE
CO SOUNDER
BASE
UNKNOWN
DEVICE
IDNet Error Messages
Type
INVALID ADDRESS
DUPLICATE ADDRESS
OUT OF RANGE
HEAD MISSING
UNKNOWN DEVICE
TrueAlarm ionization/CO sensor (standard base)
TrueAlarm ionization/CO sensor (sounder base)
TrueAlarm heat/CO sensor (standard base)
TrueAlarm heat/CO sensor (sounder base)
TrueAlarm photo/heat/CO sensor (standard base)
TrueAlarm photo/heat/CO sensor (sounder base)
4-20ma Analog Monitor ZAM
TrueAlarm sounder base (no head inserted)
TrueAlarm relay base (no head inserted)
TrueAlarm isolator base (no head inserted
TrueAlarm CO sensor base (no head inserted)
TrueAlarm CO sensor base with sounder (no head inserted)
Unrecognized device type
Description
A device was found at one of the following
addresses: 0, 251-255. The IDNet channel only
supports addresses 1-250.
More than one device was found set to the same
address.
A TrueAlarm sensor was found to have an analog
value that is out of range. This is most likely a dirty
sensor heat. Replace or clean the head.
A sensor head is not installed in a TrueAlarm base.
The TSIT has encountered a device that it is unable
to recognize. This occurs for several reasons:
More than one device is set to the same
address (run a duplicate address test).
Bad device.
A newer device type was found that is not
supported by the version of your TSIT
software.
19
19