Chuphotic MOON-i MO850i User Manual

Line interactive ups with stabilizer

Advertisement

Quick Links

Specification

Model
MO850i MO900i MO1000i MO1100i MO1250i MO1600i
850/325 900/390 1000/480 1100/550 1250/750 1600/960
Power Rate(VA/W)
Input Voltage
Output Voltage (AVR)
Output Voltage (Backup)
Battery Capacity
SLA 12V 5.4Ah x 1
Backup Time
Charging Time
Over / Under Voltage, Over Load, Shot Circuit Protection
Protection System
Low Battery Shutdown Fault and Battery Replacement
Transfer Time
LED Display
Normal, Backup, Overload, Low Battery, Battery Replacement
Audible Alam
Backup mode, Low battery, Overload, Fault
AC Line Surge Protector
1,000,000W in 100
Tel / ADSL Surge TVSS
Standard Certification
ISO9001/14001, TIS.1291 1-2553, 2-2553, 3-2555, CE : IEC62040
Environment
0-45
Dimensions (WxHxD)mm.
Weight kg.
4.3
4.6

OPERATION AND TEST THE UPS

Test UPS on battery back-up, switch off utility supply and observe 'backup indicator'
lights. Also your PC should continue to function normally.
1. Self-testing while Turn ON
Before turning on the UPS, the red/yellow/green led will be bright twice by turns.
then the UPS will be ready for operation.
2. Silence Function
In Battery Mode, shortly press the switch will enable or disable the buzzer.
But when UPS is low battery or overload, the buzzer can not be silenced.
3. Overload Protection
When UPS is overloaded while operating, which is not solved by the user in time,
it will cut off the output automatically after short time.
4. Autorun DC Start & AC Start
In DC mode, UPS discharges till battery run out and cut off, UPS autorun when
AC recover.
5. Low Battery shutdown
When the battery is about to be exhausted, UPS will shut down automatically to
protect battery's life.
6. Turn Off UPS
1. AC Normal UPS will cut off the output and goes to AC standby mode by
pressing the switch.
2. Backup
Press the switch, the UPS will be turned off after a long beep.
7. Manual Self-testing
User need to check the UPS ready for operation, Press the botton two time quickly
then UPS self test, UPS transfer AC to Backup and Backup to AC.

TROUBLE SHOOTING

The trouble shooting chart covers most of the difficulties that you may encounter
under normal working conditions. If the UPS fails to operate properly, please review
the following steps before calling the service center.
1. Is the UPS plugged into a correct working outlet?
2. Is the line voltage within the rating specified?
3. Is the Fuse or Breaker / Circuit Protector on back panal open?
4. UPS has used long time > 2 Year that is short backup time or fault.
Please submit the following information when you call for service.
1. Model No. & Serial No.
2. Date of problem.
3. Full desciption of problem UPS.
220 Vac -34%, +32% (145-290 Vac)
220 Vac +10% (198-242 Vac)
220 Vac +3% (213.4-226.6 Vac)
SLA 12V 7.2Ah x 1
7.2Ah x 2 9.4Ah x 2
15-40min (Depened on Load)
Batt. Cap.90% in 3-6 Hours
4-10msec
/ 160 Joules in 2 ms
s
µ
Tel / Fax / ADSL / RJ11 / RJ45
°
C / RH 0-90% Non condensing
100x330x155
146x345x162
5.0
5.2
8.5
UPS can not be turned
ON
Red LED continuous
bright with a beep every
8 seconds
Red LED continuous
bright with a beep every
1 seconds
10.2
Back-up time less than
specified
MO850i / MO900i /
MO1000i / MO1100i
1. Power
In▲TEL/ADSL▼Out
AC
INPUT
SURGE LASER PRINTER
TROUBLE SHOOTING CHART
UPS is not connecting
Please connect to AC
to AC and overloaded
and reduce the load
Replace the Fuse or Reset
The input Fuse is burn
the breaker, remove some
or Breaker is off
load and check if the load
is short-circuit or faulty
Please check the AC
AC Input voltage is too
Input Voltage
low
Please send to the
The UPS is failure
agency to repair
UPS suddenly turns to
Save the data promptly
Battery mode in spite of
and Shut down the
utility line present
operating system
Backup time less than
Close load and recharge
1 minute (low battery)
immediately
Battery problem
Replace the new battery
Use more load over
Recharge the battery for
atleast 12 hours and
Battery is not fully
retest the backup time
charged
Use UPS > 2 year
Replace the new battery
Charging unit fault
Please send to the
agency to repair
Front Panel
MO1250i / MO1600i
2. Backup
3. Normal
4. Overload
Rear Panel
CB 7A/250V
Press to Reset
OUTPUT UPS
OUTPUT UPS
AC INPUT
In▲TEL/ADSL▼Out
OUTPUT UPS

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MOON-i MO850i and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Chuphotic MOON-i MO850i

  • Page 1 Specification TROUBLE SHOOTING CHART Model MO850i MO900i MO1000i MO1100i MO1250i MO1600i 850/325 900/390 1000/480 1100/550 1250/750 1600/960 Power Rate(VA/W) Input Voltage 220 Vac -34%, +32% (145-290 Vac) UPS is not connecting Please connect to AC Output Voltage (AVR) 220 Vac +10% (198-242 Vac) to AC and overloaded and reduce the load Output Voltage (Backup)
  • Page 2 The Yellow LED flashes, with continuous Buck-2Boost The UPS is supplying conditioned beeping. UPS protects itself at this time. utility power to its outlets. Please move some load. OVERLOAD AUTOMATIC AC SURGE BATTERY PROTECTION VOLTAGE PROTECTION REGULATION Chuphotic.User’s Manual English-27.MOON-i 850-1600VA.Rev1.40/2019...

This manual is also suitable for:

Moon-i mo900iMoon-i mo1000iMoon-i mo1100iMoon-i mo1250iMoon-i mo1600i