EEPROM location diagram
The EEPROM (IC10) is mounted on an IC socket. Use a pair of tweezers, etc. to remove it. When installing it,
adjust its orientation as shown in the diagram below.
During EEPROM removal / installation, take care not to bend IC leads.
P.C. board (MCC-1403)
Table 2
CODE No. table (Please record the objective unit data at field)
DN
Item
01
Filter sign lighting time
02
Dirty state of filter
03
Central control address
06
Heating suction temp shift
0C
PRE-DEF indication selection
0F
Cooling only
10
Type
11
Indoor unit capacity (See below table)
12
Refrigerant line address
13
Indoor unit address
14
Group address
28
Automatic restart from power cut
2A
Option input selection (CN080)
2b
Thermostat output selection (T10
2E
Input selection (T10
32
Sensor selection
60
Timer set (Wired remote control)
Indoor unit capacity (CODE No. [11])
Setup data
Model
0001*
Invalid
0001
007 type
0002
0003
009 type
0004
0005
012 type
0006
0007
015 type
0008
* Initial value of EEPROM installed on the supplied service P.C. board
All manuals and user guides at all-guides.com
EEPROM (IC10)
When installing the EEPROM, align its
notch with that of the IC socket.Notch
IC socket
)
)
Setup data
Model
0009
018 type
0010
021 type
0011
024 type
0012
027 type
0013
030 type
0014
0015
036type
0017
048 type
– 86 –
Notch
Notch
EEPROM
Memo
0001: 150 hour
0000: Standard
0099: Unfixed
0000: No shift
0000: Standard
0000: Heat pump
Depending on model type
According to capacity type
0099: Unfixed
0099: Unfixed
0099: Unfixed
0001:Available
0002: External emergency input
0000: Thermostat ON
0000: Operation input
0000: Available
0000: Available
At shipment