Huazheng HZDZ-S3 User Manual

Huazheng HZDZ-S3 User Manual

Portable three phase power quality analyzer

Advertisement

Quick Links

HZDZ-S3 Portable Three Phase
Power Quality Analyzer
USER MANUAL
aHuazheng Electric Manufacturing(Baoding) Co.,Ltd

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HZDZ-S3 and is the answer not in the manual?

Questions and answers

Summary of Contents for Huazheng HZDZ-S3

  • Page 1 HZDZ-S3 Portable Three Phase Power Quality Analyzer USER MANUAL aHuazheng Electric Manufacturing(Baoding) Co.,Ltd...
  • Page 2: Table Of Contents

    Content Preface............................... 1 I Functions and Features........................ 2 II Technical Specifications......................4 III Structural Appearance........................ 5 (I) Size of the shell structure and terminal arrangement........... 5 (II) Keyboard..........................8 IV LCD screen...........................9 V Usage............................18 (I) Measurement of parameters of three-phase four-wire connection mode devices 19 (II) Measurement of parameters of three-phase three-wire connection mode devices20 (III) Measurement of waveform display section..............
  • Page 3: Preface

    Preface Power quality refers to the quality of the AC power supply via the utility grid to the user, which normally means the good or bad situation of the electric energy in transmission line. Power quality problems are mainly caused by the load side of the terminal. For example, impact reactive load will lead to serious fluctuates to power network voltage, and decrease the quality of power supply.
  • Page 4: I Functions And Features

    When it is interfered or contaminated, grid power quality can’t reach the national standards, so it has to be targeted on the grid power quality improvement. To understand the actual situation of power quality, you must have the appropriate equipment to test and analysis the actual situation. Counter the domestic condition, our company developed the professional power quality analysis instrument, which is suitable for the country.
  • Page 5 power quality caused by a variety of electrical equipment at different operating conditions. Record and store trend of electrical parameter, such as voltage, current, active power, reactive power, apparent power, frequency, and phase at a regular time. 9. It can do electrical equipment adjustment and dynamic monitoring during operation, and help users to solve the power adjustment and commission process problems.
  • Page 6: Technical Specifications

    easy to operate. 19. High-capacity, high-performance lithium-ion rechargeable battery is equipped inside, which can continuously work for more than 10 hours if the battery is fully charged. 20. It has a small size, light weight, easy to carry. It can be used both as site testing measurement and as the standard measurement equipment in laboratory.
  • Page 7: Structural Appearance

    Fundamental current tolerance: ≤1% F.S. Phase between fundamental voltage and current measurement error: ≤0.2 ° Percentage of harmonic voltage measurement error: ≤0.1% Percentage of harmonic current measurement error: ≤0.2% Three phase voltage unbalance error: ≤0.2% Voltage deviation error: ≤0.2% Voltage fluctuation error: ≤0.2% 3.
  • Page 8 (电能质量测试仪:power quality analyzer 参数设置:Parameter Setting 电气测 试 : Electrical Testing 谐 波 测 试 : Harmonics Testing 频谱分析:Spectrum Analysis 波形显示:Waveform Display 矢量分 析:Vector Analysis 电压闪变:Voltage Flicker 历史数据:Historical Data 国标查询:GB Query 移动存储:Removable Storage 磁盘查 询:Disk Reading 系统校准:System Calibration 存储:storage 查询:query 退出:quit 设置:set 切换:shift 自检:self-checking...
  • Page 9 信号:Signal A 相钳:phase-A clamp B 相钳:phase-B clamp C 相钳:phase-C clamp Including: Voltage input terminals: UA 、 UB 、 UC 、 UN; Clamp current transformer ports (phase-A clamp, phase-B clamp, phase-C clamp); Signal port(reserved function). A right side view of the instrument is shown at right, other parts of interface of the lower portion can be exposed when the rear holder is opened, which includes the...
  • Page 10: (Ii) Keyboard

    (II) Keyboard There are 30 keys on the keyboard, namely: switch, storage, query, set, ↑, ↓, ←, → , quit, self-checking , help, figure 1, figure 2 (ABC), figure 3 (DEF), figure 4 (GHI), figure 5 (JKL), figure 6 (MNO), figure 7 (PQRS), figure 8 (TUV), figure 9 (WXYZ), figure 0, the decimal point, #, auxiliary functions button F1, F2, F3, F4, F5.
  • Page 11: Lcd Screen

    screen. Figure (character) key: It is used for inputting parameter settings (you can input figures or characters). Decimal point key: It is used to input a decimal point when setting parameters. # Key: Reserved function, not available. F1, F2, F3, F4, F5 keys: Auxiliary function keys (shortcuts). It is used to quickly access the auxiliary function interface or implement corresponding function as prompt message says.
  • Page 12 name of the menu is selected. Related functions prompt will be shown in the blue bar at the bottom of the screen. Press Enter key to enter the corresponding functional testing and setting; Upper right corner of the screen shows the remaining power percentage of the built-in rechargeable battery, according to which users can determine whether you need to charge the instrument;...
  • Page 13 method: Press Enter key to make the figures turn red, then press the corresponding figure keys to enter data, and then press Enter key to complete. ●CT ratio: refers to the ratio value of current transformer used by the device under test. Input method: Press Enter key to make the figures turn red, then press the corresponding figure keys to enter data, and then press Enter key to complete.
  • Page 14 January 12, 2013, enter 20130112 to confirm. ● Setting Time: Input method: Press Enter key to make the figures turn red, then press the corresponding figure keys to enter data, and then press Enter key to complete. For example: 11:45:07, enter 114507 to confirm. ●...
  • Page 15 To display data from measured point of the transformer primary side and secondary side, Figure at right shows three-phase voltage, current amplitude from primary side, and phase angle between each phase voltage and current; (电能质量测试仪: power quality analyzer 测试参数 【一次】 : measurement parameter[primary side] 测试功率...
  • Page 16 various harmonics, which is represented as valid value and percentage of the fundamental wave. It represents 1-63 harmonics in tabular. You can switch tabular of (01-21) times, (22-42) times and (43-63) of the harmonic content by ↑, ↓ keys. Press F1 to lock the current screen for easy reading, and press F2 to continue to refresh. Press Escape key to return to the main menu.
  • Page 17 The bottom of the screen is an indicator, indicating that operations can be carried out. Press F1 to lock the current screen for easy reading, and press F2 to continue to refresh so that you can continue viewing from 1 to 64 harmonic phase voltage. Press Escape key to return to the main menu.
  • Page 18 测试数据:measurement data 接线分析:connection analysis 相序:phase sequence 更 正系数:modifying coefficient 感性:susceptible 容性:tolerance 按【F1】锁定,【退出】 返回:press[F1] to lock,[quit] to back) three-phase current (two-phase when two elements) and each phase angle reference to U when two elements). You can visually determine whether the three-phase metering device is correct, and tolerance-susceptible relationship between loads of each phase through this screen.
  • Page 19 10. "GB Query" Interface (电能质量测试仪:power quality analyzer 额定电压:rated voltage 短路容量:short circuit capacity 供电容量:Power Supply Capacity 协 议容量:Agreement Capacity 次数:times 电流:current 电压:voltage 按【退出】返 回主菜单:press[quit] back to main menu) "GB Query" Interface as shown at right, shows international standard of 2 to 25 times voltage and current harmonic calculated based on the nominal voltage, short circuit capacity, power supply capacity, agreement capacity (setting in "Parameter Setting").
  • Page 20: Usage

    contents of the internal memory of the instrument, including name of the stored files, size, total disk capacity and remaining available storage space. (电能质量测试仪:power quality analyzer 文件夹列表:folder list 无文件 夹:No folders 记录文件夹列表:record folder list 按【退出】返回 主菜单:press[quit]back to main menu) 13. "System Calibration" Interface Not available for users, omit.
  • Page 21: (I) Measurement Of Parameters Of Three-Phase Four-Wire Connection Mode Devices

    take off the voltage connector of the device under test after the test is completed, and then remove the voltage lines on instrument side. (This provision is particularly important, or it may cause a major accident) Here's illustration about different test items. Measurement parameters three-phase...
  • Page 22 with a green wire, and connect phase-C voltage terminal of the test equipment and phase-C voltage terminal of the instrument with a red wire; Three clamp current transformers are used to measure A, B, C three-phase current of the device. You can view measurement results in "Testing Parameters"...
  • Page 23: (Iii) Measurement Of Waveform Display Section

    equipment and phase-C voltage terminal of the instrument. You can view the measurement results in the "Testing Parameters" screen after done with wiring. (III) Measurement of waveform display section 1 Purpose for testing You can view waveform of each parameter, understand the phase relationship between each parameter (lead or lag), observe distortion situation of waveform, analyze the causes for distortion generated, and whether the PT and CT are overload through this project.
  • Page 24: (V) Analysis Of Voltage Harmonic Section

    Perform wiring in accordance with wiring diagram for testing three-phase three-wire devices if the device is a three-Phase three-wire connection mode one. Go to the "Spectrum Analysis Interface" for testing after wiring. (V) Analysis of voltage harmonic section 1 Purpose for testing This function is used to display the numerical and percentage content of 2-64 harmonic content of the three-phase voltage parameters, in order to determine whether power quality of the measured voltage signal is good or bad.
  • Page 25: (Vii) Unbalance Measurement Section

    content of the three-phase current parameters, in order to determine whether power quality of the measured current signal is good or bad. 2 Testing method (被测设备: tested equipment 信号: signal 相钳:phase-A clamp B 相钳:phase-B clamp C 相钳:phase-C clamp 电流谐波测试接线图:Current Harmonics Test Wiring Diagram) Specific wiring as shown at right: In this project, three-phase current signal is simultaneously accessed.
  • Page 26: Battery Maintenance And Charging

    设备:tested equipment A 相钳:phase-A clamp B 相钳:phase-B clamp 信号:signal C 相钳:phase-C clamp 不平衡度测试接线图:Unbalance Test Wiring Diagram) Connect phase-A voltage terminal of the test equipment and phase-A voltage terminal of the instrument with a yellow wire, and connect phase-B voltage terminal of the test equipment and phase-B voltage terminal of the instrument with a green wire, and connect phase-C voltage terminal of the test equipment and phase-C voltage terminal of the instrument with a red wire;...
  • Page 27: Notes

    VII Notes 1. Do not touch the metal parts of the test line during measurement process to avoid electrical injury. 2. Measurement wiring must operate in strict accordance with the instructions to ensure personal safety. 3. Better use of power outlet with ground. 4.

Table of Contents