Loopdrive – User and installation manual
1.1.

Loopdrive components

Loopdrive system comprises of two types of devices which play different roles in the system:
FRONT
1. MODE/EARTH indicator
2. OPEN indicator
3. SHORT indicator
4. SERVICE button
5. RESET button
6. ID rotary switch
7. LOOP PRIMARY output connector
8. LOOP SECONDARY output connector
9. Power amplifier connector
10. Loopdrive bus DIN rail connector
LDB (LoopDrive Booster) – is the central unit installed in the Voice Alarm System rack,
directly between the amplifier and loudspeaker line. Mounted on a DIN rail LDB works
as the DC power supply for FIMs and can also generate special service commands to FIMs.
LDB is responsible for monitoring and reporting faults globally (per loudspeaker loop):
-
Loop short (entire loop)
-
Loop open (entire loop)
-
T-branch short (any T-branch)
-
T-branch open (any T-branch)
-
Earth leakage (amplifier input, entire loop, any T-branch)
-
Amplifier input open
TOP

ƒ
BOTTOM
FAULT OUTPUT CONTACT
ˆ
SIDE
Š
RS485 B
RS485 A
GND
+24V/48VDC DC