Approved Breakaway Connections - Greenheck ODFD Series Installation, Operation And Maintenance Manual

Table of Contents

Advertisement

Approved Breakaway Connections

All breakaway connections described below may utilize the following duct sealants: PA2084T duct sealant adhesive
manufactured by Precision, DP1010 water base duct sealant manufactured by Design Polymerics, Grey Pookie,
Ductmate PROseal®, or CL Ward S Seal in accordance with SMACNA recommendations.
Transverse Joints
The transverse joints shown below are approved as breakaway connections.
• A maximum of two #10 (19 mm) sheet metal screws on each side and on the bottom may be used. The screws
should be located in the center of the slip pocket and penetrate both sides of the slip pocket.
• Dampers up to 20 in. (508 mm) high may use transverse joints on the top and bottom and Drive Slip joints (see
Figure 11) on the sides.
Plain "S" Slip
Hemmed "S"
Inside Slip Joint
Standing "S" (Alt.)
(Bar Reinforced)
Figure 10
Round and Oval Duct Breakaway
Connections
Factory furnished duct collars, type R and O, are also
considered breakaway (see Figure 12).
Round or flat oval ducts connected to Type R or O damper
collars shall be attached with #10 (19 mm) sheet metal
screws as follows:
• Ducts up to 22 in. (558 mm) wide (or dia.) and less shall
have three screws.
• Ducts larger than 22 in. (558 mm) wide (or dia.) up to
and including 36 in. (914 mm) wide (or dia.) shall have
five screws.
8
Out of Wall Fire and Combination Fire Smoke Dampers
Slip
Double "S"
Slip
Standing "S"
Standing "S" (Alt.)
Standing "S"
Standing "S"
(Angle Reinforced)
Drive Slip Joint
Figure 11
Duct
Type R and O
factory furnished
duct collars qualify
as breakaway
connections.
Duct
Type R, O
Figure 12: Type R and O Transition
r
Wall or Floo
Sleeve
Damper
Type B
r
Wall or Floo
Sleeve
Damper
®