Out of wall fire and combination fire smoke dampers

Advertisement

Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with these instructions will result in voiding of the product warranty and may result in personal injury
and/or property damage.
These instructions apply to 1
or stud walls and 2) concrete floors. Specific requirements in these instructions are mandatory. Dampers must be
installed in accordance with these instructions to meet the requirements of UL 555 and/or UL 555S.
Note: Combination fire smoke and fire dampers are manufactured and labeled for either vertical or horizontal
installation. The dampers must be installed in accordance with labeling.
Receiving and Handling
Upon receiving dampers, check for both obvious
and hidden damage. If damage is found, record all
necessary information on the bill of lading and file
a claim with the final carrier. Check to be sure that
all parts of the shipment, including accessories, are
accounted for.
Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust and the weather is
highly recommended. Do not store at temperatures in
excess of 100°F (38°C).
This manual is the property of the owner and is required for future maintenance. Please leave it with the owner when
the job is complete.
hour rated fire and combination fire smoke dampers mounted in: 1) masonry, block,
1
2
Out of Wall Fire and Combination Fire
ODFD-XXX, OFD-XXX, OFSD-XXX SERIES
1
Hour Fire & Combination Fire Smoke Dampers
1
2

Table of Contents

General Information . . . . . . . . . . . . . . . . . . . . . . . . 2
Pre-Installation Guidelines . . . . . . . . . . . . . . . . . . . 2
Electrical Guidelines . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Preparation of Openings . . . . . . . . . . . . . . . . . . 3
Sleeves and Wall/Floor Openings . . . . . . . . . . . 4
to Wall/Floor Openings . . . . . . . . . . . . . . . . . . . 5
Duct to Sleeve Connection . . . . . . . . . . . . . . . 6-7
Device Connections . . . . . . . . . . . . . . . . . . . . . . 8
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Safety Warning
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury
or death. Read the installation, operating, and
maintenance instructions thoroughly before installing
or servicing this equipment.
Out of Wall Fire and Combination Fire Smoke Dampers
Document 461337
Smoke Dampers
Out of Wall or Out of Floor
1

Advertisement

Table of Contents
loading

Summary of Contents for Greenheck ODFD Series

  • Page 1: Table Of Contents

    Document 461337 Out of Wall Fire and Combination Fire Smoke Dampers ODFD-XXX, OFD-XXX, OFSD-XXX SERIES ⁄ Hour Fire & Combination Fire Smoke Dampers Out of Wall or Out of Floor Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described.
  • Page 2: General Information

    This work should be performed by a qualified (Refer to NFPA 90A). electrician. Verify power before wiring actuator. Greenheck is not responsible for any damage to, or 8) The Code Authority Having Jurisdiction (AHJ) must failure of the unit caused by incorrect field wiring. To...
  • Page 3: Preparation Of Openings

    Preparation of Openings • Frame wall openings as shown below (see Figure 1, 2, & 2A). • Gypsum wall board must be fastened 12 in. (305mm) on center (O.C.) to all stud and runner flanges surrounding opening (see Figure 1, 2, & 2A). •...
  • Page 4: Clearances Required Between Damper Sleeves And Wall/Floor Openings

    8 1/2 in. max.* For more installation methods that are approved for Masonry floor ODFD-XXX and OFD-XXX series, go to www.greenheck. Damper com. For access to inspect the damper and fusible link Figure 7: Continuing Duct - Horizontal or Vertical Mount refer to the requirements of NFPA 90A.
  • Page 5: Securing The Damper/Sleeve Assembly To Wall/Floor Openings

    Securing the Damper/Sleeve Assembly to Wall/Floor Openings Damper/sleeve assemblies must be installed in wall openings using flanges and sheet metal screws as illustrated and described below. • Flange on front (grille end) of sleeve must be a minimum of 16 ga. (1.5mm) steel and have ⁄...
  • Page 6: Duct To Sleeve Connection

    Duct to Sleeve Connection Sleeve Gauge and Connection Type Requirements The size of the damper/duct determines the required Type of Duct sleeve gauge and the required duct to sleeve to Sleeve Sleeve Gauge Duct Dimension connection (see table to the right). The sleeve thickness Connection must also not be less than the gauge of the connecting Permitted...
  • Page 7 Duct Damper Approved Breakaway Connections..Type B Round and Oval Duct Breakaway Connections Wall or Floo Type R and O Factory furnished duct collars, type R and O, are also factory furnished considered breakaway (see Figure 12). duct collars qualify Sleeve as breakaway Round or flat oval ducts connected to Type R or O damper...
  • Page 8: Actuator And Temperature Response Device Connections

    Actuator and Temperature Response Device Connections Actuator Connections Temperature Response Device Connections Electrical and/or pneumatic connections to damper actuators should be made in accordance with wiring RRL: The RRL (resettable link device) incorporates and piping diagrams developed in compliance with a single thermostat.
  • Page 9: Maintenance

    Damper Maintenance Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and jamb seals, do not use oil-based lubricants or any other lubricants that attract contaminants such as dust. Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with: •...
  • Page 10 Notes Out of Wall Fire and Combination Fire Smoke Dampers...
  • Page 11 Notes Out of Wall Fire and Combination Fire Smoke Dampers...
  • Page 12 As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Product warranties can be found online at Greenheck.com, either on the specific product page or in the literature section of the website at Greenheck.com/Resources/Library/Literature.